Castleport Test Prep

EPA 608 Leak Repair Requirements

EPA 608 leak repair requirements cover appliances with a full charge of 50 pounds or more of an ozone-depleting refrigerant or a blend containing one (§82.157). Since January 1, 2026, the separate 15-pound HFC rule has covered qualifying appliances but excluded the residential and light commercial air conditioning and heat pump subsector; both rules use these triggers (§84.106):

Annual leak-rate trigger by appliance use
Appliance useAction is required when the annual leak rate is over
Industrial process refrigeration30%
Commercial refrigeration20%
Comfort cooling and all other covered appliances10%

Once a covered appliance goes over its trigger, the owner has 30 days from the triggering refrigerant addition to find and fix the leaks. That becomes 120 days if the repair requires an industrial process shutdown. The owner can also choose to retrofit or retire the appliance under a written plan. Sources: §82.157(c)–(d), §84.106(c)–(d).

Which leak repair rule applies?

The rule depends on what refrigerant is in the appliance and how much it holds when full. The 15-pound number did not replace Section 608's 50-pound threshold. It belongs to a different rule.

Which leak repair rule applies?
Refrigerant in the applianceFull chargeFederal leak repair rule
Only an ozone-depleting refrigerant (for example, R-22, R-11, or R-123)50 lb or moreSection 608: §82.157
Only an ozone-depleting refrigerantUnder 50 lbNeither rule
A regulated HFC or a blend containing one (such as R-410A, R-404A, R-134a, or R-448A)15 lb or moreHFC rule: §84.106, except residential and light commercial air conditioning and heat pumps
A substitute that contains no regulated HFC or ODS, with a global warming potential above 5315 lb or moreHFC rule: §84.106, with the same exception
A refrigerant with a global warming potential of 53 or below that contains no regulated HFC or ODS (such as CO₂ or ammonia)AnyNeither rule
An HFC or HFC-substitute appliance under 15 lbUnder 15 lbNeither rule

"Neither rule" means neither §82.157 nor §84.106 applies to that appliance. It is not a blanket exemption from other refrigerant requirements: venting, recovery, and technician-certification rules have their own scope and exceptions (§82.154; §82.161).

Table sources: §82.157(a), §84.106(a), EPA ODS list, EPA blend compositions, and EPA GWP reference table.

A few terms, so the table reads cleanly:

  • Ozone-depleting substance (ODS): for this page, a Class I or Class II substance used as a refrigerant. Examples include CFCs and HCFCs, such as R-11 and R-22 (EPA ODS list).
  • HFC (hydrofluorocarbon): a refrigerant with no chlorine, so it doesn't deplete ozone. Many HFCs have a high global warming potential. The refrigerant-content test includes any HFC regulated under the American Innovation and Manufacturing (AIM) Act; the appliance must also meet the charge and use conditions above.
  • Global warming potential (GWP): a substance's warming effect compared with CO₂. The "above 53" test applies only to substitutes that aren't HFCs themselves. The lowest value the AIM Act assigns to a regulated HFC is 53 (EPA fact sheet, Jan. 2026, p. 1, note 4).

A blend that contains both an ODS and an HFC can meet the conditions of both rules. The HFC rule's ODS exclusion covers only appliances that contain solely an ODS (§82.157(a); §84.106(a)(3)).

For 608 exam study, EPA lists leak repair under Type II and Type III in its public test topics. That list does not establish whether a certifying organization tests the newer HFC rule, so do not treat “50 pounds for the exam, 15 pounds for the field” as an official rule. Keep the two regulations distinct and use your certifying organization's current study materials. The regulation itself says "50 or more pounds," so a 50-pound ODS appliance is covered.

What counts as full charge and appliance type?

Full charge is the amount of refrigerant the appliance needs to run normally. It is not the weight of the equipment, the amount left after a leak, or the amount you added today. EPA allows four ways to determine it:

  • the manufacturer's figure
  • a calculation from component sizes and piping
  • actual measurements
  • an established range based on the best available data about normal operating conditions, whose midpoint is used

Each independent circuit counts as its own appliance. Sources: 40 CFR 82.152, "Appliance" and "Full charge"; 40 CFR 84.102.

Classify the appliance by what it does, not by who owns it:

  • Comfort cooling is air conditioning for people in occupied buildings, such as chillers, commercial split systems, and packaged rooftop units. A store's rooftop AC is comfort cooling, not commercial refrigeration.
  • Commercial refrigeration means retail food and cold storage warehouse equipment. Supermarket racks, restaurant walk-ins, and cold storage all fit here.
  • Industrial process refrigeration (IPR) is complex, customized equipment tied to an industrial process. Industrial ice machines, equipment used directly in generating electricity, and ice rinks also count. An appliance that serves both industrial and other uses is IPR if at least half its operating capacity serves the industrial process.

The HFC rule also names refrigerated transport in its 10% group. Under Section 608, an appliance that isn't comfort cooling, commercial, or IPR falls under "other," also at 10%. Sources: §82.152; §84.106(c)(2).

Does the 15-pound HFC rule apply to home air conditioners?

No. Appliances in the residential and light commercial air conditioning and heat pump subsector are excluded from §84.106, whatever their charge. EPA describes this subsector as equipment that cools individual rooms, single-family homes, and small commercial buildings. Chillers and certain variable refrigerant flow (VRF) systems belong to other subsectors, so they are not excluded. The cited EPA description does not define "light commercial" by a pound cutoff, so classify by the equipment's subsector, not the building's name (EPA fact sheet, p. 1, note 3).

Transport refrigeration: On May 26, 2026, EPA proposed exempting road and intermodal container transport refrigeration units from the HFC leak repair rule. As of the rule text we checked (eCFR, current through September 24, 2026), the proposed exemption was not in the codified text (EPA regulatory actions; Federal Register, May 26, 2026).

How to calculate the annual leak rate

The leak rate is the percentage of the full charge the appliance would lose over a year if it kept leaking at its current pace. EPA allows two methods. The owner or operator must use the same method for every covered appliance at the facility, so you can't pick whichever method gives a lower number on a given day. Sources: §82.152, "Leak rate"; §84.102. The HFC rule allows a switch only after acquiring a facility whose method differs from the method at the owner's other facilities, if the affected appliances are not exceeding their triggers under either method and the change is documented (§84.106(b)(3)).

For a covered appliance, calculate the rate every time refrigerant is added. There are three exceptions: an addition made right after a retrofit, one made right after installing a new appliance, and an addition that qualifies as a seasonal variance (§82.157(b); §84.106(b)).

Annualizing method

Leak rate (%) = (pounds added ÷ full charge) ÷ (days since the last addition ÷ 365) × 100

  • Pounds added is the amount needed to bring the appliance back to full charge. Several additions for the same leak count together.
  • Days since the last addition is capped at 365. If more than a year has passed, use 365.

Worked example 1 (Section 608, comfort cooling)

Worked example 1 (Section 608, comfort cooling)
InputValue
ApplianceR-22 comfort cooling unit
Full charge100 lb
Refrigerant added to restore full charge4 lb
Days since the previous addition90

(4 ÷ 100) ÷ (90 ÷ 365) × 100 = 16.222…% ≈ 16.2%

That's over the 10% comfort cooling trigger, so the 30-day repair clock starts with this addition.

The trap here: 4 pounds is 4% of the charge, which looks harmless. But losing it in 90 days means losing about 16% over a year. The time factor is the whole point of annualizing.

Rolling average method

Leak rate (%) = (pounds added over the previous 365 days ÷ full charge) × 100

If the last successful follow-up verification test showed all identified leaks repaired less than a year ago, count only the pounds added since that test. This is not a January-to-December total, and you don't average the individual additions.

Worked example 2 (Section 608, commercial refrigeration)

Worked example 2 (Section 608, commercial refrigeration)
InputValue
ApplianceR-22 cold storage refrigeration system
Full charge100 lb
Additions in the past 365 days, including today's10 lb, 6 lb, 8 lb
Successful follow-up verification in that windowNone

(10 + 6 + 8) ÷ 100 × 100 = 24%

That's over the 20% commercial refrigeration trigger. Add the pounds first, then divide by the full charge. Don't multiply a rolling result by a day factor.

The first HFC calculation after January 1, 2026

The HFC rule has a transition step for each appliance's first calculation after January 1, 2026 (§84.106(b)(1)–(2)):

  • Annualizing: use 365 days as the time since the last addition.
  • Rolling average: count only pounds added since January 1, 2026.

Worked example 3 (HFC rule, comfort cooling): An R-134a chiller with an 80-lb full charge gets its first 2026 addition of 5 lb to restore full charge. Using the annualizing method with 365 days: (5 ÷ 80) ÷ (365 ÷ 365) × 100 = 6.25%. That's under the 10% trigger, so this addition doesn't start a repair clock. It still has to be recorded.

Exactly at the trigger

The rules require corrective action when the leak rate is over the trigger. A result of exactly 20.0% on a commercial system doesn't exceed 20%. When a repair is required, it must bring the rate below the trigger (§82.157(c)–(d)). Round only at the end, and never round a result down to make it pass.

What happens after an appliance goes over the trigger

The steps are nearly identical under both rules. Where they differ, the table says so.

What happens after an appliance goes over the trigger
StepWhat's requiredDeadline
1. Find the leaksA certified technician does a leak inspection that locates the leaks. Under the HFC rule, the repairs themselves must also be done by a certified technician.Within the repair window
2. RepairFix the leaks so the leak rate drops below the trigger.30 days from the refrigerant addition that showed the appliance was over its trigger, or 120 days if an industrial process shutdown is required
3. Initial verification testTest each repaired leak to show the repair holds. Do it before refrigerant is added back. If the repair required evacuating the system, test before recharging. You can repair and retest as many times as you need inside the window.Within the same 30- or 120-day window
4. Follow-up verification testTest again once the appliance is running normally, to show the repair held.Within 10 days of a successful initial test; if the appliance or isolated portion was evacuated, within 10 days of reaching normal operating conditions
5. ConfirmThe next leak rate calculation, at the next addition, must confirm that the rate is below the trigger.At the next addition
6. Ongoing leak inspectionsSee the inspection schedule below.Quarterly or yearly

Sources: §82.157(d)–(e); §84.106(c)–(e).

If testing at normal operating conditions would be unsafe or impossible, the follow-up test must instead be conducted before returning to those conditions, where practicable (§82.157(e)(2); §84.106(e)(2)). Section 608 also has a separate certification rule for work that could violate the refrigerant circuit; the comparison is not permission for an uncertified person to open an ODS system (§82.161(a)).

Methods that only show whether a system leaks don't count as a leak inspection by themselves. That includes standing pressure or vacuum decay tests, sight glass checks, receiver levels, and charging charts. They have to be paired with a method that finds where the leak is, such as an electronic or ultrasonic detector, bubbles, or a gas-imaging camera (§82.152, "Leak inspection").

Under Section 608, a repair is presumed successful if no refrigerant is added for 12 months after the repair, or if the required leak inspections find no leaks. Under the HFC rule, the 12-month period starts at the successful follow-up verification test: either no refrigerant is added during that period, or the required inspections and/or an automatic leak detection system required by §84.108 find no leaks during it (§82.157(d)(2); §84.106(d)(2)).

When parts are late, or the system is shut down

Extensions exist for specific situations, not for any delay. They cover three cases:

  • Parts: a needed part isn't available within 30 days (or 120 with a shutdown). Additional time is allowed up to 30 days after the part arrives, but no later than 180 days from when the appliance went over its trigger (270 days with an industrial process shutdown).
  • Other rules: other federal, state, or local rules make a timely repair impossible. The HFC rule adds Tribal rules.
  • Radiological contamination: the appliance is in a contaminated area, or shutting it down would cause contamination.

To use an extension, the owner must:

  • complete and verify repairs within the original window for any leaks the technician identified as a significant cause of the exceedance, if they don't need the extra time
  • document every repair effort and why the deadline can't be met
  • file the extension request with EPA within the original 30 days (or 120)

Sources: §82.157(f); §84.106(f).

Mothballing pauses the specified repair and verification deadlines, and the retrofit or retirement plan timelines—not the recordkeeping duties or the calendar-year reporting rule. EPA defines it as evacuating the appliance, or the isolated leaking section, to at least atmospheric pressure and temporarily shutting it down. Switching the power off is not mothballing. The clock picks up again on the day refrigerant is added back. Keep records of both dates (§82.152, "Mothball"; §82.157(d)(3), (i), (l)(8); §84.106(d)(3), (i), (l)(10)).

When repair isn't the answer: retrofit or retirement

A retrofit converts the appliance to a different refrigerant. Retirement means removing the refrigerant and disabling the refrigerant circuit so nobody can use the appliance again. For a covered appliance, the owner must write a retrofit or retirement plan within 30 days of the applicable event below:

  • the appliance is leaking over its trigger and the owner intends to retrofit or retire instead of repairing
  • the appliance is leaking over its trigger and the owner fails to act to find or repair the leaks
  • the appliance still leaks over its trigger after the required repairs and verification tests

The plan must include:

  • the appliance and its location
  • the current refrigerant and full charge
  • for a retrofit, the new refrigerant, its full charge, and an itemized conversion procedure
  • what happens to the recovered refrigerant and, for a retirement, to the appliance
  • a schedule of no more than one year

It must be signed by an authorized company official, dated, and kept at the site. All identified leaks must be repaired as part of any retrofit. The work must be finished within one year of the plan's date unless an extension applies. Sources: §82.157(h); §84.106(h).

If the owner establishes within 180 days of the plan's date that the appliance no longer exceeds its trigger, the owner can ask EPA to be released from the plan. The owner must agree in writing to repair all identified leaks within one year of the plan's date and submit the plan and supporting information required by §82.157(h)(5)(ii) or §84.106(h)(5)(ii). The extension options for the one-year schedule differ between the two rules; see the comparison table below.

How often are leak inspections required?

These recurring inspections apply after an appliance has gone over its trigger. They aren't a standing schedule for every appliance.

How often are leak inspections required?
Appliance after an exceedanceSection 608 (§82.157)HFC rule (§84.106)
Commercial refrigeration or IPR, full charge 500 lb or moreEvery 3 months, until 4 quarters in a row do not exceed the triggerEvery 3 months, counted from the successful follow-up verification test, until 4 quarters in a row do not exceed the trigger
Commercial refrigeration or IPR under 500 lbOnce per calendar year, until one year does not exceed the trigger (covers 50 to under 500 lb)Once per year after the successful follow-up verification test, until one year does not exceed the trigger (covers 15 to under 500 lb)
Comfort cooling and other appliancesOnce per calendar year, until one year does not exceed the triggerOnce per year after the successful follow-up verification test, until one year does not exceed the trigger

Sources: §82.157(g); §84.106(g). The owner must demonstrate the no-exceedance period through the required leak rate calculations.

Under these schedules, the size of a comfort cooling appliance never moves it to quarterly inspections. A covered office chiller with a 900-lb full charge is still on the annual schedule.

A certified technician does the inspection and checks all visible and accessible components. The exceptions are parts that are insulated, iced over, underground, or behind walls; parts that would require personnel to be more than two meters above a support surface; and parts that site personnel determine are unsafe to inspect. A continuously monitoring automatic leak detection (ALD) system can replace scheduled inspections for the parts it monitors only if it meets the applicable requirements in §82.157(g)(4) or §84.106(g)(4). Section 608 requires annual auditing or calibration and the specified detection performance. The HFC provision also incorporates §84.108(c)–(g) and (i), including annual auditing and calibration. Any parts it doesn't monitor still need inspections.

Mandatory ALD under the HFC rule: For covered commercial refrigeration and IPR appliances with a full charge of 1,500 lb or more of refrigerant containing a regulated HFC (or a qualifying substitute with a GWP above 53), §84.108 sets these installation deadlines:

  • Installed on or after January 1, 2026: at installation or within 30 days.
  • Installed from January 1, 2017 through December 31, 2025: by January 1, 2027.

Section 608's leak repair rule does not require ALD; it's an option there (40 CFR 84.108; EPA fact sheet, Table 2).

For an appliance subject to §84.108, an ALD alert also creates a response duty under §84.108(h): calculate the leak rate within 30 days of the alert, or 120 days where an industrial process shutdown would be necessary. The owner may repair the identified leak before adding refrigerant, but must still calculate within that alert window. If the calculated rate exceeds the trigger, the full §84.106 leak repair requirements apply. Keep the ALD installation, annual audit/calibration, alert, and leak-location records for at least three years (§84.108(i)).

What records and EPA reports are required?

The leak repair duties fall mainly on the owner or operator. Anyone who adds or removes refrigerant from a covered appliance must give the owner a service record when the job is done. That record covers the appliance, date, parts, work done, the technician's name, and the type and amount of refrigerant. Technicians who do leak inspections and verification tests must hand over those results too. Sources: §82.157(b), (l); §84.106(b), (l).

Keep records for at least three years. Keep full-charge records until three years after the appliance is retired. For the HFC rule, the full charge of every covered appliance had to be determined by January 1, 2026, or at installation for newer equipment, and the records include the installation date. Sources: §82.157(l); §84.106(l)(1).

The 125% chronic leak report

An appliance covered by the applicable leak repair rule that leaks 125% or more of its full charge in a calendar year needs a report to EPA by March 1 of the following year. This is about the refrigerant actually lost from January through December, not an annualized projection. It's separate from the 10/20/30% repair triggers. For 2026, the report is due March 1, 2027. Sources: §82.157(j); §84.106(j).

Quick math: on an HFC commercial refrigeration appliance with a 40-lb full charge, 125% is 50 lb lost in one calendar year.

Where reports go

  • Section 608: Send notifications to 608reports@epa.gov. Submissions containing confidential business information go by mail to the address in §82.157(m).
  • HFC rule: File electronically through EPA's HAWK platform. To get access, register in EPA's Central Data Exchange (CDX) with the Leak Reporter role. EPA's forms cover repair extensions, retrofit or retirement extensions, requests to be released from a plan, chronic leak reports, and purged-refrigerant notices (EPA reporting resources).

Don't send an HFC filing to the Section 608 email address.

A leak repair worksheet

Use this checklist to organize a leak event or to study the sequence. It's a checklist, not a compliance certificate, and it doesn't replace the records the rules require.

A leak repair worksheet
FieldWhat to record or check
W01 ApplianceAppliance or circuit ID, location, and the owner or operator
W02 Refrigerant and full chargeRefrigerant, full charge in pounds, how it was determined, and installation date for the HFC rule
W03 Rule and use§82.157, §84.106, both, or neither; any exclusion; comfort cooling, commercial refrigeration, IPR, or other
W04 Addition historyDate and pounds of this addition, earlier additions and their dates, and any exception (retrofit, new install, seasonal variance)
W05 CalculationThe facility's method, all inputs, the unrounded result, the trigger, and whether the rate is over it
W06 Repair responseDate of the triggering addition; 30- or 120-day deadline; leak inspection and repair results; verification of significant leaks within the original window when seeking an extension; any extension request or mothball dates
W07 VerificationInitial test date and result; whether the system was evacuated; date it returned to normal operation; follow-up test date and result
W08 Continuing dutiesInspection schedule, ALD duties if they apply, and retrofit or retirement plan date and completion date if required
W09 Calendar-year checkTotal lost this calendar year compared with 125% of full charge; if required, report route and March 1 due date
W10 Records keptService records, inspection and test results, calculations, ALD installation/audit/calibration/alert records, plans, EPA submissions and responses, and how long to keep each

If you don't know the refrigerant, full charge, or dates, you can't finish the rule or rate decision. Missing information doesn't make an appliance exempt.

Section 608 vs. the HFC rule: the differences that matter

The trigger percentages and basic repair windows match. These details don't:

Section 608 vs. the HFC rule: the differences that matter
TopicSection 608 (§82.157)HFC rule (§84.106)
CoversFull charge of 50 lb or more of a Class I or Class II refrigerant, or a blend containing oneFull charge of 15 lb or more of refrigerant containing a regulated HFC, or a qualifying non-HFC substitute with GWP above 53
Left outAppliances containing only substitute refrigerants, such as HFCsAppliances containing only an ODS; residential and light commercial AC and heat pumps
In forceCurrent trigger rates since January 1, 2019; substitute-only appliances excluded April 10, 2020January 1, 2026
Who must be certifiedLeak inspection expressly requires a certified technician; §82.161 separately governs refrigerant-circuit work during repairsLeak inspection and leak repairs expressly require a certified technician
Refrigerated transportCounts as "other," 10%, if it holds 50 lb or more of an ODSNamed in the 10% group; a road/intermodal-container exemption is proposed, not present in the reviewed codified text
Automatic leak detectionOptional in place of inspections if §82.157(g)(4) is metCovered commercial refrigeration/IPR of 1,500 lb or more has the installation-date deadlines above; qualifying ALD may also replace inspections
Annual inspection timingOnce per calendar yearOnce per year, counted from the successful follow-up verification test
Reports and extension requestsEmail to 608reports@epa.gov; confidential submissions use the prescribed mailing routeEPA's HAWK platform, signed by an authorized company official
Extra time on a retrofit or retirementConditional extensions for IPR and federally owned commercial/comfort-cooling equipment; 18 months total to retire when the replacement uses an exempt substituteFor IPR only (including radiological contamination)
First leak rate calculationNo special ruleFirst calculation after January 1, 2026 uses 365 days (annualizing) or only pounds added since that date (rolling)

Sources: §82.157; §84.106; §84.108; EPA fact sheet, Table 2.

Old numbers you'll still see

Older study guides mix rules from different years. Here's what each date changed:

Old numbers you'll still see
DateWhat changedWhat it means for you
Before January 1, 2019Triggers were 35% for commercial refrigeration and IPR, and 15% for comfort coolingHistorical. For a covered appliance under the current rules, the commercial refrigeration trigger is over 20%.
January 1, 2019Current triggers took effect: 30% IPR, 20% commercial refrigeration, 10% comfort cooling and otherThese are the Section 608 numbers to learn
April 10, 2020Appliances containing only substitute refrigerants, such as HFCs, were removed from §82.157Section 608 leak repair covers ODS refrigerants and blends containing them at the 50-lb threshold. Other Section 608 rules, such as the venting ban, still apply to HFCs.
January 1, 2026The separate HFC leak repair rule (§84.106) took effect at 15 lbA new rule, not a change to Section 608's 50-lb threshold

Sources: EPA, Regulatory Updates: Section 608; §82.157(a), (c); §84.106(a).

A quick way to organize any leak repair question: identify the refrigerant and full charge, classify the use, calculate the rate, then apply the response and records. It's our study aid, not an EPA rule.

Practice: 14 leak repair scenarios

These are original, unofficial practice questions written by Castleport Test Prep. They are not EPA exam items. Each answer and explanation sits right under its question. Your score reflects these 14 questions only. It isn't an official score or a prediction of your exam result. The set combines Section 608 concepts with current HFC-rule scenarios; it is not a claim about an exam bank's HFC coverage. Stated appliance charges are full charges, and “HFC” in these scenarios means a regulated HFC or a blend containing one.

Question 1 · LR-01

HFC rule · Leak repair requirements (applicability)

It's 2026. A cold storage warehouse refrigeration unit holds 30 lb of R-407C, an HFC blend. Which federal leak repair rule applies?

Choose one answer for LR-01
Reveal answer and explanation for LR-01

Answer: B. §84.106, with a 20% trigger.

Why: Cold storage is commercial refrigeration. The appliance holds 15 lb or more of a refrigerant containing an HFC, so the HFC rule applies from January 1, 2026, at the 20% commercial trigger.

Why not the others: A applies the 50-lb line, which now governs only ozone-depleting refrigerants. C is wrong because §82.157 hasn't covered HFC-only appliances since April 10, 2020. D uses the comfort cooling rate.

Source: §84.106(a), (c)(2); §84.102, "Commercial refrigeration"; EPA, Compositions of Refrigerant Blends

Review this rule.

Answer: B. §84.106, with a 20% trigger.

Why: Cold storage is commercial refrigeration. The appliance holds 15 lb or more of a refrigerant containing an HFC, so the HFC rule applies from January 1, 2026, at the 20% commercial trigger.

Why not the others: A applies the 50-lb line, which now governs only ozone-depleting refrigerants. C is wrong because §82.157 hasn't covered HFC-only appliances since April 10, 2020. D uses the comfort cooling rate.

Source: §84.106(a), (c)(2); §84.102, "Commercial refrigeration"; EPA, Compositions of Refrigerant Blends

Review this rule.

Question 2 · LR-02

HFC rule · Leak repair requirements (applicability)

An 18-lb R-410A split system cools a single-family home, and it's leaking above 10% a year. Does §84.106 require leak repair?

Choose one answer for LR-02
Reveal answer and explanation for LR-02

Answer: D. No, because the residential and light commercial AC and heat pump subsector is excluded.

Why: §84.106(a)(3)(ii) excludes this subsector regardless of charge size. That exclusion does not remove the separate certification and venting requirements that apply to work on an R-410A system.

Why not the others: A ignores the exclusion. B invents an installation-date rule. C reaches "no" for the wrong reason: the HFC rule is based on HFC content, not ozone depletion.

Source: §84.106(a)(3); EPA fact sheet, p. 1; §82.154(a), venting and exceptions; §82.161(a), certification; EPA, Compositions of Refrigerant Blends

Review this rule.

Answer: D. No, because the residential and light commercial AC and heat pump subsector is excluded.

Why: §84.106(a)(3)(ii) excludes this subsector regardless of charge size. That exclusion does not remove the separate certification and venting requirements that apply to work on an R-410A system.

Why not the others: A ignores the exclusion. B invents an installation-date rule. C reaches "no" for the wrong reason: the HFC rule is based on HFC content, not ozone depletion.

Source: §84.106(a)(3); EPA fact sheet, p. 1; §82.154(a), venting and exceptions; §82.161(a), certification; EPA, Compositions of Refrigerant Blends

Review this rule.

Question 3 · LR-03

Section 608 and HFC rules · Leak repair requirements (applicability)

A rooftop unit cooling an office holds 45 lb of R-22. Which federal leak repair rule applies?

Choose one answer for LR-03
Reveal answer and explanation for LR-03

Answer: C. Neither rule.

Why: §82.157 starts at 50 lb. §84.106 excludes appliances containing only an ozone-depleting refrigerant, and R-22 is an HCFC.

Why not the others: A misses the 50-lb threshold. B misses the ODS-only exclusion. D fails for both reasons.

Source: §82.157(a); §84.106(a)(3)(i); EPA, Ozone-Depleting Substances

Review this rule.

Answer: C. Neither rule.

Why: §82.157 starts at 50 lb. §84.106 excludes appliances containing only an ozone-depleting refrigerant, and R-22 is an HCFC.

Why not the others: A misses the 50-lb threshold. B misses the ODS-only exclusion. D fails for both reasons.

Source: §82.157(a); §84.106(a)(3)(i); EPA, Ozone-Depleting Substances

Review this rule.

Question 4 · LR-04

HFC rule · Leak repair requirements (leak rate calculation)

A restaurant walk-in cooler holds 25 lb of R-448A, which contains HFCs. A technician adds 3 lb to restore full charge, 200 days after the last addition. The facility uses the annualizing method. This is a later §84.106 calculation, not its first after January 1, 2026. What's the result?

Choose one answer for LR-04
Reveal answer and explanation for LR-04

Answer: A. 21.9%, over the 20% commercial refrigeration trigger.

Why: (3 ÷ 25) ÷ (200 ÷ 365) × 100 = 21.9%. A restaurant walk-in is retail food equipment, which makes it commercial refrigeration with a 20% trigger.

Why not the others: B skips annualizing. C applies the IPR trigger. D multiplies by the time fraction instead of dividing by it.

Source: §84.102, "Leak rate"; §84.106(b)(1), (c)(2); EPA, Compositions of Refrigerant Blends

Review this rule.

Answer: A. 21.9%, over the 20% commercial refrigeration trigger.

Why: (3 ÷ 25) ÷ (200 ÷ 365) × 100 = 21.9%. A restaurant walk-in is retail food equipment, which makes it commercial refrigeration with a 20% trigger.

Why not the others: B skips annualizing. C applies the IPR trigger. D multiplies by the time fraction instead of dividing by it.

Source: §84.102, "Leak rate"; §84.106(b)(1), (c)(2); EPA, Compositions of Refrigerant Blends

Review this rule.

Question 5 · LR-05

HFC rule · Leak repair requirements (leak rate calculation)

A 200-lb HFC supermarket case line needs 15 lb to restore full charge, 146 days after its last addition. The facility uses the annualizing method. This is a later §84.106 calculation, not its first after January 1, 2026, and there are no outstanding duties from an earlier exceedance. What does the leak repair rule require?

Choose one answer for LR-05
Reveal answer and explanation for LR-05

Answer: C. Record the addition and the 18.8% leak rate; no repair is triggered.

Why: (15 ÷ 200) ÷ (146 ÷ 365) × 100 = 18.75%, which is under the 20% commercial refrigeration trigger. The owner still keeps the service record and the leak rate calculation.

Why not the others: A compares 18.8% with the wrong trigger. B is an arithmetic slip. D confuses the 500-lb inspection-frequency line with the 15-lb applicability threshold.

Source: §84.106(b), (c)(2), (l)(2)

Review this rule.

Answer: C. Record the addition and the 18.8% leak rate; no repair is triggered.

Why: (15 ÷ 200) ÷ (146 ÷ 365) × 100 = 18.75%, which is under the 20% commercial refrigeration trigger. The owner still keeps the service record and the leak rate calculation.

Why not the others: A compares 18.8% with the wrong trigger. B is an arithmetic slip. D confuses the 500-lb inspection-frequency line with the 15-lb applicability threshold.

Source: §84.106(b), (c)(2), (l)(2)

Review this rule.

Question 6 · LR-06

HFC rule · Leak repair requirements (repair timeline)

A 2,000-lb HFC process chiller at a chemical plant needs 150 lb to restore full charge, 90 days after its last addition. The facility uses the annualizing method, and this is not the appliance's first §84.106 calculation after January 1, 2026. Repairing it requires shutting down the industrial process. What's the repair deadline?

Choose one answer for LR-06
Reveal answer and explanation for LR-06

Answer: D. 120 days, because an industrial process shutdown is required.

Why: (150 ÷ 2,000) ÷ (90 ÷ 365) × 100 ≈ 30.4%, which is over the 30% IPR trigger. The window is 120 days from the triggering addition when the repair requires an industrial process shutdown.

Why not the others: A is the normal window, but this repair needs a shutdown. B misreads "over": 30.4% exceeds 30%. C is the retrofit or retirement schedule.

Source: §84.106(b)(1), (c)(2), (d); §84.102, Leak rate

Review this rule.

Answer: D. 120 days, because an industrial process shutdown is required.

Why: (150 ÷ 2,000) ÷ (90 ÷ 365) × 100 ≈ 30.4%, which is over the 30% IPR trigger. The window is 120 days from the triggering addition when the repair requires an industrial process shutdown.

Why not the others: A is the normal window, but this repair needs a shutdown. B misreads "over": 30.4% exceeds 30%. C is the retrofit or retirement schedule.

Source: §84.106(b)(1), (c)(2), (d); §84.102, Leak rate

Review this rule.

Question 7 · LR-07

Section 608 and HFC rules · Leak repair requirements (verification tests)

A covered appliance exceeded its leak rate trigger. Fixing the leak required evacuating part of the system, and follow-up testing at normal operating conditions is safe and practicable. When must the initial and follow-up verification tests happen?

Choose one answer for LR-07
Reveal answer and explanation for LR-07

Answer: B. The initial test before refrigerant is added back; the follow-up within 10 days of the system reaching normal operating conditions.

Why: When the repair requires evacuation, the initial verification test comes before recharging, inside the repair window. The follow-up comes within 10 days of the appliance returning to normal operating conditions.

Why not the others: A merges two different tests. C borrows the 12-month presumption and the inspection schedule. D is wrong because both tests are required for the repair described.

Source: §82.157(e); §84.106(e)

Review this rule.

Answer: B. The initial test before refrigerant is added back; the follow-up within 10 days of the system reaching normal operating conditions.

Why: When the repair requires evacuation, the initial verification test comes before recharging, inside the repair window. The follow-up comes within 10 days of the appliance returning to normal operating conditions.

Why not the others: A merges two different tests. C borrows the 12-month presumption and the inspection schedule. D is wrong because both tests are required for the repair described.

Source: §82.157(e); §84.106(e)

Review this rule.

Question 8 · LR-08

HFC rule · Leak repair requirements (extensions)

An HFC commercial refrigeration rack has exceeded its 20% trigger. A compressor needed for repair will not be available within the original 30-day window, and no industrial process shutdown is required. Which statement is accurate?

Choose one answer for LR-08
Reveal answer and explanation for LR-08

Answer: D. The owner can get up to 30 days after delivery, capped at 180 days from the exceedance. The owner must request it within 30 days and complete and verify repairs on time for significant leaks that do not need extra time.

Why: §84.106(f) allows this extension when the necessary part is unavailable within the original repair window. The owner must complete and verify repairs of significant leaks that do not need extra time within that window, document the repair efforts, and request the extension from EPA within 30 days.

Why not the others: A is wrong because the extension has conditions and a filing requirement. B confuses the repair deadline with the retrofit or retirement schedule. C describes one Section 608 retrofit extension, not the repair extension.

Source: §84.106(f)

Review this rule.

Answer: D. The owner can get up to 30 days after delivery, capped at 180 days from the exceedance. The owner must request it within 30 days and complete and verify repairs on time for significant leaks that do not need extra time.

Why: §84.106(f) allows this extension when the necessary part is unavailable within the original repair window. The owner must complete and verify repairs of significant leaks that do not need extra time within that window, document the repair efforts, and request the extension from EPA within 30 days.

Why not the others: A is wrong because the extension has conditions and a filing requirement. B confuses the repair deadline with the retrofit or retirement schedule. C describes one Section 608 retrofit extension, not the repair extension.

Source: §84.106(f)

Review this rule.

Question 9 · LR-09

Section 608 and HFC rules · Leak repair requirements (retrofit or retirement)

A covered appliance still leaks over its trigger after the required repairs and both verification tests. The applicable repair window has ended, and no extension or mothballing suspension applies. What's next?

Choose one answer for LR-09
Reveal answer and explanation for LR-09

Answer: A. Write a retrofit or retirement plan within 30 days and finish the work within one year of the plan's date.

Why: Continued leakage over the trigger after the required repairs and verification tests is one of the three events that require a plan.

Why not the others: B doesn't meet the rule. C mixes in the chronic leak report, which depends on 125% lost in a calendar year and is due March 1. D invents a limit on repair attempts.

Source: §82.157(h); §84.106(h)

Review this rule.

Answer: A. Write a retrofit or retirement plan within 30 days and finish the work within one year of the plan's date.

Why: Continued leakage over the trigger after the required repairs and verification tests is one of the three events that require a plan.

Why not the others: B doesn't meet the rule. C mixes in the chronic leak report, which depends on 125% lost in a calendar year and is due March 1. D invents a limit on repair attempts.

Source: §82.157(h); §84.106(h)

Review this rule.

Question 10 · LR-10

HFC rule · Leak detection (leak inspection requirements)

A 900-lb HFC centrifugal chiller cools an office tower. It went over its trigger and was repaired and verified. No qualifying ALD system is replacing its scheduled inspections. How often must it now be leak-inspected?

Choose one answer for LR-10
Reveal answer and explanation for LR-10

Answer: C. Once a year after the successful follow-up verification test, until it goes a year without exceeding 10%.

Why: Quarterly inspections apply only to commercial refrigeration and IPR of 500 lb or more. This comfort cooling appliance is on the annual schedule, counted from the successful follow-up verification test. The owner must demonstrate the no-exceedance year through the required leak rate calculations.

Why not the others: A applies the 500-lb line to the wrong category. B isn't in the rule. D is wrong because verification tests don't replace inspections.

Source: §84.106(g)(1)(iii)

Review this rule.

Answer: C. Once a year after the successful follow-up verification test, until it goes a year without exceeding 10%.

Why: Quarterly inspections apply only to commercial refrigeration and IPR of 500 lb or more. This comfort cooling appliance is on the annual schedule, counted from the successful follow-up verification test. The owner must demonstrate the no-exceedance year through the required leak rate calculations.

Why not the others: A applies the 500-lb line to the wrong category. B isn't in the rule. D is wrong because verification tests don't replace inspections.

Source: §84.106(g)(1)(iii)

Review this rule.

Question 11 · LR-11

HFC rule · Leak detection (chronically leaking appliances)

An HFC commercial refrigeration appliance has a full charge of 40 lb. What is the minimum refrigerant loss in one calendar year that triggers a chronic leak report?

Choose one answer for LR-11
Reveal answer and explanation for LR-11

Answer: B. 50 lb.

Why: The threshold is 125% or more of full charge in a calendar year: 1.25 × 40 = 50 lb. The report is due by March 1 of the following year.

Why not the others: 20 lb is 50% and 40 lb is 100%, both below the threshold. 60 lb is 150% and would also require reporting, but it is not the minimum.

Source: §84.106(j)

Review this rule.

Answer: B. 50 lb.

Why: The threshold is 125% or more of full charge in a calendar year: 1.25 × 40 = 50 lb. The report is due by March 1 of the following year.

Why not the others: 20 lb is 50% and 40 lb is 100%, both below the threshold. 60 lb is 150% and would also require reporting, but it is not the minimum.

Source: §84.106(j)

Review this rule.

Question 12 · LR-12

HFC rule · Leak repair requirements (leak rate calculation)

A 120-lb HFC walk-in freezer system has 10 lb removed each fall because of the change in season. In spring, 8 lb is added back, within the same 12-month period. Does the spring addition need a leak rate calculation?

Choose one answer for LR-12
Reveal answer and explanation for LR-12

Answer: D. No, it's a seasonal variance, but the owner must record that it used this exception and the amounts removed and added.

Why: A seasonal variance is a seasonal removal followed by adding back the same amount or less within one 12-month period. It's excluded from the calculation, but it has to be documented.

Why not the others: A ignores the exception. B drops the recordkeeping. C invents a size condition.

Source: §84.102, "Seasonal variance"; §84.106(b), (l)(12)

Review this rule.

Answer: D. No, it's a seasonal variance, but the owner must record that it used this exception and the amounts removed and added.

Why: A seasonal variance is a seasonal removal followed by adding back the same amount or less within one 12-month period. It's excluded from the calculation, but it has to be documented.

Why not the others: A ignores the exception. B drops the recordkeeping. C invents a size condition.

Source: §84.102, "Seasonal variance"; §84.106(b), (l)(12)

Review this rule.

Question 13 · LR-13

HFC rule · Leak detection (automatic leak detection)

A supermarket installs a new 1,800-lb HFC rack system in March 2026. What does the HFC rule require for leak detection?

Choose one answer for LR-13
Reveal answer and explanation for LR-13

Answer: A. An automatic leak detection system at installation or within 30 days, audited and calibrated every year.

Why: Commercial refrigeration of 1,500 lb or more installed on or after January 1, 2026 needs ALD at installation or within 30 days.

Why not the others: B is the deadline for systems installed from 2017 through 2025. C is the Section 608 position, not the HFC rule's for this size. D reverses the rule: the ALD mandate covers commercial refrigeration and IPR, not comfort cooling.

Source: §84.108(a)–(d)

Review this rule.

Answer: A. An automatic leak detection system at installation or within 30 days, audited and calibrated every year.

Why: Commercial refrigeration of 1,500 lb or more installed on or after January 1, 2026 needs ALD at installation or within 30 days.

Why not the others: B is the deadline for systems installed from 2017 through 2025. C is the Section 608 position, not the HFC rule's for this size. D reverses the rule: the ALD mandate covers commercial refrigeration and IPR, not comfort cooling.

Source: §84.108(a)–(d)

Review this rule.

Question 14 · LR-14

Section 608 and HFC rules · Leak repair requirements (mothballing)

Before the 30-day repair window ends, an owner evacuates a leaking appliance to atmospheric pressure and shuts it down for the season. What happens to the deadline?

Choose one answer for LR-14
Reveal answer and explanation for LR-14

Answer: C. It's paused, and it resumes on the day refrigerant is added back.

Why: Evacuating to at least atmospheric pressure and temporarily shutting down meets the definition of mothballing, which suspends the clock. The owner keeps records of both dates.

Why not the others: A ignores the mothballing rule. B is wrong because a pause isn't a cancellation. D confuses mothballing with the industrial process shutdown window.

Source: §82.152, "Mothball"; §82.157(d)(3); §84.106(d)(3)

Review this rule.

Answer: C. It's paused, and it resumes on the day refrigerant is added back.

Why: Evacuating to at least atmospheric pressure and temporarily shutting down meets the definition of mothballing, which suspends the clock. The owner keeps records of both dates.

Why not the others: A ignores the mothballing rule. B is wrong because a pause isn't a cancellation. D confuses mothballing with the industrial process shutdown window.

Source: §82.152, "Mothball"; §82.157(d)(3); §84.106(d)(3)

Review this rule.

What to do with your misses: Reread the section of this page that each missed question points to, then try to state the rule without looking. For broader practice across Core and Types I, II, and III, use the EPA 608 Universal practice test.

Quick answers

Can I keep topping off a leaking system?

Not as a way to avoid the rules. On a covered appliance, an addition normally requires a new leak rate calculation; the retrofit, new-installation, and seasonal-variance exceptions are explained above. If the rate is over the trigger, the repair clock starts, and adding more refrigerant doesn't satisfy it. A result at or below the trigger does not create a new repair trigger, but it does not erase outstanding duties from an earlier exceedance (§82.157(b)–(h); §84.106(b)–(h)). EPA doesn't treat leaks during normal operation as venting violations. Knowingly releasing a non-exempt refrigerant during service or disposal is a separate prohibition, subject to the rule's specified exceptions (EPA venting prohibition; §82.154(a)).

Who is responsible, the technician or the owner?

The owner or operator, unless a provision says otherwise. Certified technicians must do the leak inspections, and the HFC leak repair provision expressly requires certified technicians for the repairs. They must also hand the owner service, inspection, and verification records (§82.157(a)–(b); §84.106(c)(1)).

Does the leak repair rule apply to R-22 systems?

Yes, under Section 608 if the full charge is 50 lb or more. An R-22-only appliance is excluded from the HFC leak repair rule (§82.157(a); §84.106(a)(3)(i)).

For the rest of the exam, including test types, topics, and how the Universal test is scored, see our EPA 608 exam prep guide.

Sources

We checked each source below on September 28, 2026. The eCFR regulation pages showed Title 40 as current through September 24, 2026.

Last verified: September 28, 2026, for the federal regulations, EPA guidance pages, reporting instructions, and exam topic list above. We didn't review state or local rules, test EPA's reporting platform, or see any certifying program's question bank. The worked examples, worksheet, and practice questions are original educational material.

By Castleport Test Prep Editorial Team

Castleport Test Prep is an independent exam prep publisher. We are not affiliated with, endorsed by, or approved by the U.S. Environmental Protection Agency or any EPA-approved certifying organization. Exam and credential names are used only to identify their subjects, and trademarks belong to their respective owners. This page explains federal rules for study. It isn't legal or compliance advice for a specific appliance, and it does not address state or local requirements.