Free NHIE Practice Test: 60 Questions With Explanations
This free NHIE practice test has 60 original, unofficial questions for the National Home Inspector Examination, with answers and explanations—no signup. Pick your answer, then open the explanation under each question.
Practice questions
Question 1 of 60
Domain 1 · Electrical · Aluminum branch wiring
You inspect a house built in 1969. Several 15- and 20-amp branch circuits use solid aluminum conductors. At three receptacles, someone has added short copper pigtails joined to the aluminum with standard twist-on wire connectors. What should your report say?
A. Report the copper pigtails as a completed, permanent repair that needs no further action by the client or an electrician.
B. Advise the client to coat each aluminum connection with antioxidant compound to finish the repair.
C. Report the aluminum wiring and twist-on pigtails; refer to a qualified electrician for a recognized permanent repair.
D. State that the home should not be occupied until all aluminum wiring is removed.
Show answer and explanation for Question 1
Correct answer: C. Report the aluminum wiring and twist-on pigtails; refer to a qualified electrician for a recognized permanent repair.
The CPSC found that standard twist-on connectors used to pigtail aluminum branch wiring overheated in its testing and don't solve the problem. It describes copper rewiring and COPALUM repairs, with AlumiConn as the next-best permanent alternative when COPALUM is unavailable. Your job here is to report what you saw and send it to a qualified electrician; the observations don't justify choosing a repair for the client or condemning the house.
Why the other choices are weaker
- A. Twist-on pigtails are exactly the method CPSC says is not a permanent fix.
- B. Antioxidant alone isn't one of CPSC's recognized permanent repairs, and this is not a do-it-yourself connection repair.
- D. This overstates the finding. CPSC describes repair options short of full rewiring; these observations alone don't establish an occupancy ruling.
Sources: CPSC Pub. 516, Repairing Aluminum Wiring (Permanent repairs and alternatives; PDF pp. 6–9, especially AlumiConn p. 8 and twist-on connectors p. 9); EBPHI content outline — topic coverage (Domain 1, Task 5, C.4 (solid-conductor aluminum branch wiring); coverage, not a technical-answer source)
Item ID: NHIE-D1T5-01
Question 2 of 60
Domain 1 · Site conditions · Pool access barrier
The agreed inspection includes the backyard pool's access barrier. Its only pedestrian gate swings into the pool area. When you open it partway and let go, it stays open. Which report entry is BEST?
A. Note the gate as functional, since it swings freely, opens and closes without binding, and shows no visible damage.
B. Recommend that the owners keep the gate locked whenever children visit.
C. Report it as a safety defect: the gate should open outward, self-close, and self-latch.
D. Omit the gate, because pools are never part of a home inspection.
Show answer and explanation for Question 2
Correct answer: C. Report it as a safety defect: the gate should open outward, self-close, and self-latch.
CPSC's barrier guidelines call for pedestrian gates that open out from the pool and are self-closing and self-latching, so a child pushing on the gate can't get in. A gate that stays open defeats the barrier, which makes this a safety finding rather than a convenience note.
Why the other choices are weaker
- A. "Opens and closes" isn't the standard. The barrier only works if the gate closes and latches by itself.
- B. Behavior advice doesn't correct the defect, and the hazard exists whether or not anyone remembers to lock it.
- D. The question expressly includes the access barrier in the agreed inspection. A pool exclusion in some basic standards doesn't erase that agreed scope.
Sources: CPSC Pub. 362, Safety Barrier Guidelines for Residential Pools (Pedestrian gates, printed p. 11 / PDF p. 13); EBPHI content outline — topic coverage (Domain 1, Task 1, C (pool and spa access barriers); coverage, not a technical-answer source)
Item ID: NHIE-D1T1-01
Question 3 of 60
Domain 1 · Exterior · Garage door auto-reverse
An attached garage has an automatic door with photo-eye sensors that stop and reverse the door when you break the beam. During the manufacturer's specified contact-reversal test, the closing door contacts the test obstruction and keeps pushing down instead of reversing. What should you report?
A. Report a safety defect: contact reversal isn't working; refer to a garage door technician.
B. Report it as acceptable, because the working photo-eye sensors already provide the protection the door opener requires.
C. Report it as acceptable if the door stops moving within 10 seconds of contact.
D. Recommend disconnecting the photo-eyes so the reversal setting can be tested.
Show answer and explanation for Question 3
Correct answer: A. Report a safety defect: contact reversal isn't working; refer to a garage door technician.
The door has failed its specified contact-reversal test. Working photo-eyes don't excuse a failed contact reversal. Federal entrapment-protection rules include prescribed laboratory obstruction tests, but those test dimensions and timings are not a universal home-inspection procedure. Report the failed safety function and refer it to a garage door technician.
Why the other choices are weaker
- B. The photo-eyes and contact-reversal function address different obstruction situations. Passing one test doesn't erase failure of the other.
- C. Ten seconds is not a substitute for the manufacturer's specified test. The observed door kept pushing instead of reversing.
- D. Disabling a safety device adds risk and is not a remedy for a failed reversal test.
Sources: 16 CFR Part 1211, Safety Standard for Automatic Residential Garage Door Operators (§§1211.6–1211.8, particularly §1211.7 laboratory obstruction tests); EBPHI content outline — topic coverage (Domain 1, Task 2, D.4 (obstruction sensors, automatic reverse); coverage, not a technical-answer source)
Item ID: NHIE-D1T2-01
Question 4 of 60
Domain 2 · Further evaluation and urgent action · Gas odor at the meter
While walking the exterior, you notice a strong natural-gas odor at the gas meter and hear a faint hiss at one fitting. The sellers are inside the house. What should you do first?
A. Finish the inspection, then describe the odor and hissing in the written report.
B. Tighten the leaking fitting with a wrench, then confirm the odor has stopped.
C. Warn the occupants without entering the danger area, move away, and call the gas utility's emergency line from a safe location.
D. Run each gas appliance to see whether the odor gets stronger near any of them.
Show answer and explanation for Question 4
Correct answer: C. Warn the occupants without entering the danger area, move away, and call the gas utility's emergency line from a safe location.
A suspected gas leak needs action now, not only a written report later. The gas utility's safety instructions say to leave the affected area, avoid switches, doorbells and other ignition sources, and call from a safe location. Warn others without entering the danger area; do not operate appliances or try to repair the leak.
Why the other choices are weaker
- A. A report written hours later doesn't protect the people inside right now.
- B. Do not attempt a repair during a suspected gas leak; leave and get emergency responders involved.
- D. Operating gas equipment during a suspected leak adds risk and doesn't change what you need to do.
Sources: New Jersey Natural Gas, Smell Gas? (Emergency instructions: leave, avoid ignition sources, telephone from a safe location); EBPHI content outline — topic coverage (Domain 2, Task 4, item 3 (life-threatening hazards such as a gas leak); coverage, not a technical-answer source)
Item ID: NHIE-D2T4-01
Question 5 of 60
Domain 1 · Cooling · How air conditioning moves heat
A central air conditioner is running in cooling mode. Which statement BEST describes what the system is doing?
A. The indoor coil releases cold refrigerant vapor into the air passing over it.
B. The outdoor unit draws cooler outside air in and blows it through the supply ducts, replacing the warmer air in the house.
C. The air filter removes heat from return air before it reaches the indoor coil.
D. Refrigerant absorbs indoor heat, moisture condenses on the cold indoor coil, and the outdoor coil releases heat outside.
Show answer and explanation for Question 5
Correct answer: D. Refrigerant absorbs indoor heat, moisture condenses on the cold indoor coil, and the outdoor coil releases heat outside.
An air conditioner doesn't make "cold." It moves heat. Refrigerant absorbs heat at the indoor coil and releases it outdoors. Moisture can condense on the cold indoor coil and drain away; the water does not become part of the refrigerant circuit.
Why the other choices are weaker
- A. Refrigerant stays sealed inside the system. Air passes over the coil; refrigerant isn't added to the air.
- B. The outdoor condensing unit rejects heat; it doesn't supply cooled outdoor air through the house's ducts.
- C. A filter traps particles. It doesn't remove heat, and a clogged one actually reduces cooling.
Sources: U.S. DOE, Energy Saver 101: Home Cooling (PDF p. 1, How an Air Conditioner Works and Common Air Conditioner Problems); EBPHI content outline — topic coverage (Domain 1, Task 6, A.3 (refrigerant cycle); coverage, not a technical-answer source)
Item ID: NHIE-D1T6-01
Question 6 of 60
Domain 1 · Roof · Kick-out flashing
Where the bottom of a sloped roof meets a two-story sidewall, there is no kick-out (diverter) flashing. The siding just below that spot is stained and soft. What is the purpose of the missing component?
A. To ventilate the attic space where the roof meets the wall.
B. To support the end of the gutter so it doesn't sag.
C. To direct roof runoff away from the wall, usually into the gutter.
D. To replace the house wrap behind the siding in that area.
Show answer and explanation for Question 6
Correct answer: C. To direct roof runoff away from the wall, usually into the gutter.
PNNL's Building America guide describes kick-out flashing as a piece at the bottom of a roof section beside a wall that directs runoff away from the wall and usually into a gutter. Without it, water running down the step flashing can be driven into or behind the siding. The stained, soft siding is consistent with that, so you'd report both and recommend a roofer or siding contractor.
Why the other choices are weaker
- A. Kick-out flashing is a water-control part, not a ventilation part.
- B. Gutters are supported by hangers or brackets. Flashing diverts water.
- D. Flashing works with the weather-resistant barrier; it doesn't replace it.
Sources: PNNL, Flashing at Roof-Wall Intersections in Existing Homes (Scope; Description; Ensuring Success); EBPHI content outline — topic coverage (Domain 1, Task 3, C (roof flashings); coverage, not a technical-answer source)
Item ID: NHIE-D1T3-01
Question 7 of 60
Domain 3 · Pre-inspection agreement · Purpose of the pre-inspection agreement
A first-time buyer asks why you need a signed agreement before you inspect. Which explanation is BEST?
A. It guarantees the client that every defect in the house will be found.
B. It shifts responsibility for hidden defects to the real estate agent.
C. It sets the scope, limitations, and terms before work begins.
D. It's a formality that only matters if the client files a complaint.
Show answer and explanation for Question 7
Correct answer: C. It sets the scope, limitations, and terms before work begins.
EBPHI's outline describes the written pre-inspection agreement as establishing the rights and responsibilities of the inspector and client, including scope, limitations, and terms of service. Its value is that expectations are settled before the inspection, not argued about afterward.
Why the other choices are weaker
- A. No visual inspection can promise that. Agreements typically state limitations, not guarantees.
- B. An inspection agreement is between the inspector and the client; it doesn't assign duties to an agent.
- D. Its main job is to set expectations up front, and the outline treats it as a core professional responsibility.
Sources: EBPHI exam overview packet and content outline (Domain 3, Task 1: agreement scope, parties and timing)
Item ID: NHIE-D3T1-01
Question 8 of 60
Domain 1 · Structure · Horizontal foundation crack
In a concrete-block basement, one long wall has a wide horizontal crack about halfway up. The wall is visibly pushed inward along the crack. What is the BEST approach?
A. Call it a normal shrinkage crack and recommend monitoring it for change.
B. Report a structural concern consistent with lateral pressure; refer to a structural engineer.
C. Recommend sealing the crack and painting the wall to stop moisture entry.
D. Estimate the repair cost so the client can negotiate a credit with the seller.
Show answer and explanation for Question 8
Correct answer: B. Report a structural concern consistent with lateral pressure; refer to a structural engineer.
HUD's inspection guide describes horizontal cracking and inward bowing of masonry foundation walls under lateral loading. Here, the visible displacement makes this a structural concern, not a routine cosmetic crack. Describe the location, cracking and movement, then refer for structural evaluation rather than claiming that the exact cause or repair is already known.
Why the other choices are weaker
- A. Shrinkage cracks don't usually come with a wall pushed out of plane. The displacement is the key fact.
- C. Cosmetic sealing doesn't address movement and could hide its progress.
- D. The facts don't establish a repair design or price. A cost estimate cannot replace evaluation of the displaced wall.
Sources: HUD, Residential Rehabilitation Inspection Guide, part 2 (§4.4, printed pp. 47–48 / PDF pp. 38–39: horizontal bowing of masonry foundation walls); EBPHI content outline — topic coverage (Domain 1, Task 4, A.4 and A.6 (typical defects; applied forces incl. hydrostatic pressure); coverage, not a technical-answer source)
Item ID: NHIE-D1T4-01
Question 9 of 60
Domain 1 · Plumbing and fuel distribution · Capped relief valve
A tank-type water heater's temperature-and-pressure (T&P) relief valve discharge pipe has been capped with a threaded plug, apparently to stop drips. What should you report?
A. Acceptable, because the plug prevents water damage from a dripping valve.
B. Tell the homeowner to remove the plug and lift the test lever to check it.
C. Note it as a routine maintenance item for the homeowner to bring up with the plumber at the next water heater service visit.
D. A serious safety defect: the relief path is blocked; recommend immediate plumber repair.
Show answer and explanation for Question 9
Correct answer: D. A serious safety defect: the relief path is blocked; recommend immediate plumber repair.
A T&P relief valve provides automatic temperature and pressure protection for a water heater. Capping its discharge defeats that protection. Watts' safety instructions prohibit restrictions in that discharge path. Report the blocked relief path immediately and recommend qualified plumber correction before further water-heater operation.
Why the other choices are weaker
- A. Stopping the drip by blocking the relief path removes the safety protection. A dripping valve needs evaluation, not a plug.
- B. A blocked relief path can be dangerous. Do not direct a homeowner to uncap or test a potentially hot, pressurized system; it needs qualified service.
- C. This is a safety defect, not routine maintenance.
Sources: Watts TAG-100, T&P relief-valve safety instructions (Single-page safety tag: relief discharge must not be restricted; installation and service warnings); ASHI Standard of Practice (§13.2.C–F: unsafe procedures and inoperable/safety controls); EBPHI content outline — topic coverage (Domain 1, Task 10, D.7–D.8 (T&P relief defects; lack of relief valve); coverage, not a technical-answer source)
Item ID: NHIE-D1T10-01
Question 10 of 60
Domain 1 · Insulation, moisture and ventilation · Exposed insulation facing
In a finished basement storage room, ordinary kraft-paper-faced fiberglass batts, not a fire-rated exposed-facing product, are installed between the wall studs with the paper facing left exposed. What should you report?
A. Report the exposed combustible facing as a defect needing correction.
B. No comment, since the batts have an appropriate R-value for a basement wall.
C. Report it only as a cosmetic finish issue in the storage room.
D. Recommend removing all basement insulation to restore wall airflow.
Show answer and explanation for Question 10
Correct answer: A. Report the exposed combustible facing as a defect needing correction.
Ordinary kraft paper facing is combustible and should not be left exposed. Knauf's guidance distinguishes it from facing specifically rated for exposed use. The finding is about exposure, not the insulation's R-value.
Why the other choices are weaker
- B. R-value doesn't address the fire concern from an exposed combustible facing.
- C. The manufacturer identifies a fire concern from ordinary exposed kraft facing, not just an unfinished appearance.
- D. Overreach. The issue is exposed facing, not the presence of insulation.
Sources: Knauf, Faced vs. Unfaced Insulation (Facing/fire-safety discussion); EBPHI content outline — topic coverage (Domain 1, Task 8, A.5–A.6 (exposed paper backing; fire hazards); coverage, not a technical-answer source)
Item ID: NHIE-D1T8-01
Question 11 of 60
Domain 2 · Limitations · Blocked attic access
The only attic hatch is in a closet packed floor to ceiling with stored boxes. You can't reach it without moving the owner's belongings. What should your report say?
A. State that the attic appears satisfactory, since no ceiling stains or other signs of roof leaks were seen in the rooms below.
B. Leave the attic out of the report, because it wasn't accessible during the visit.
C. State that the house has no attic, since no usable access was found.
D. State that the attic wasn't inspected, why, and recommend inspecting it once accessible.
Show answer and explanation for Question 11
Correct answer: D. State that the attic wasn't inspected, why, and recommend inspecting it once accessible.
EBPHI's outline asks you to describe what was NOT inspected and why, including inaccessible areas. ASHI's Standard of Practice does not require moving personal belongings. A clear limitation tells the client exactly what remains unknown.
Why the other choices are weaker
- A. You can't report an area as satisfactory when you didn't inspect it.
- B. Silence hides a gap the client needs to know about.
- C. Blocked access isn't the same as no attic. That statement would be false.
Sources: ASHI Standard of Practice (§2.2.B.4; §13.2.F.3: inaccessible areas and moving personal property); EBPHI content outline — topic coverage (Domain 2, Task 2, items 1–2 (common limitations; limitations of a visual inspection); coverage, not a technical-answer source)
Item ID: NHIE-D2T2-01
Question 12 of 60
Domain 1 · Mechanical exhaust · Dryer exhaust duct
During an inspection that includes dryer exhaust, the exhaust runs through white plastic accordion duct that is partly crushed against the wall. Lint has collected in the folds. What should you report?
A. Recommend cleaning lint out of the existing duct and leaving it in place.
B. No comment, since the duct is part of the appliance rather than the house.
C. Report the crushed plastic duct as a fire hazard; recommend metal duct.
D. Recommend venting the dryer into the garage to shorten the duct run.
Show answer and explanation for Question 12
Correct answer: C. Report the crushed plastic duct as a fire hazard; recommend metal duct.
CPSC recommends replacing plastic or foil accordion duct with rigid or corrugated semi-rigid metal duct. It explains that flexible plastic duct traps lint more easily and is more likely to kink or crush, cutting airflow. Blocked airflow can cause excessive heat and fires. EBPHI's outline lists plastic dryer ducts as a typical defect.
Why the other choices are weaker
- A. Cleaning helps, but the duct material and crushing are the defect.
- B. The dryer exhaust is included in this inspection; its material and condition are reportable.
- D. Exhaust should go outdoors. Venting into a garage moves lint and moisture indoors.
Sources: CPSC Pub. 5022, Overheated Clothes Dryers Can Cause Fires (Single-page duct material, lint and airflow guidance); ASHI Standard of Practice (§11.1: clothes dryer exhaust); EBPHI content outline — topic coverage (Domain 1, Task 9, A.5–A.6 (plastic dryer ducts; fire hazards); coverage, not a technical-answer source)
Item ID: NHIE-D1T9-01
Question 13 of 60
Domain 1 · Life safety · Smoke alarm coverage
A two-story house with a basement has one smoke alarm, in the upstairs hallway outside three bedrooms. There are no alarms inside the bedrooms, on the main floor, or in the basement. What should you report?
A. Coverage is adequate, because the hallway alarm sits right outside the bedrooms.
B. Report missing alarms in the bedrooms, on the main floor, and in the basement.
C. Recommend a hallway carbon monoxide alarm, which will also detect smoke.
D. Recommend adding one more smoke alarm in the kitchen near the range.
Show answer and explanation for Question 13
Correct answer: B. Report missing alarms in the bedrooms, on the main floor, and in the basement.
The U.S. Fire Administration recommends smoke alarms inside and outside each bedroom and sleeping area, and on every level of the home. One hallway alarm leaves the bedrooms and two whole levels uncovered. EBPHI's outline includes smoke alarm placement under life safety.
Why the other choices are weaker
- A. Current guidance calls for alarms inside bedrooms and on every level, not just one hallway.
- C. A CO alarm doesn't replace a smoke alarm unless it's a listed combination unit.
- D. The kitchen is the wrong priority, and one more alarm still leaves the bedrooms and levels uncovered.
Sources: U.S. Fire Administration, Smoke Alarms (Opening placement recommendation; Where do I put smoke alarms?); EBPHI content outline — topic coverage (Domain 1, Task 13, item 3 (smoke and CO alarm placement); coverage, not a technical-answer source)
Item ID: NHIE-D1T13-01
Question 14 of 60
Domain 1 · Heating · Heat pump in heating mode
On a cool morning, an electric air-source heat pump is heating the house. Its supplemental electric heat is off. Where is the delivered heat mainly coming from?
A. Gas combustion taking place inside the outdoor condensing unit.
B. The supplemental electric heat strips inside the air handler.
C. The indoor blower motor, which converts electricity into most of the heat it delivers as it spins.
D. Heat pulled from the outdoor air and moved indoors by the refrigerant cycle.
Show answer and explanation for Question 14
Correct answer: D. Heat pulled from the outdoor air and moved indoors by the refrigerant cycle.
ENERGY STAR explains that a heat pump runs the air-conditioning cycle in reverse in winter, extracting heat energy from outside and transferring it into the home. With backup heat off, the refrigerant cycle is doing the work.
Why the other choices are weaker
- A. This electric heat pump moves heat through a refrigerant cycle; it is not obtaining heat by burning gas in the outdoor unit.
- B. The question says the supplemental heat is off.
- C. The blower moves air across the coil. It isn't the heat source.
Sources: ENERGY STAR, How Does a Heat Pump Work? (Heating/winter operation); EBPHI content outline — topic coverage (Domain 1, Task 6, A.3 (heat pumps); Task 7, A.3; coverage, not a technical-answer source)
Item ID: NHIE-D1T7-01
Question 15 of 60
Domain 1 · Fireplaces and fuel-burning appliances · Cracked chimney
At the top of a masonry chimney serving a wood stove, you see an open crack running through the crown and into the flue liner. What should your report say?
A. Describe it as a cosmetic crack that is typical of older masonry chimneys.
B. Report it as a safety concern; recommend a chimney professional's evaluation before use.
C. Recommend patching it with exterior caulk to keep rain out of the flue.
D. Leave the crack out of the report, since the stove lit easily and appeared to draft normally during the inspection.
Show answer and explanation for Question 15
Correct answer: B. Report it as a safety concern; recommend a chimney professional's evaluation before use.
EPA's Burn Wise guidance (an archived program page) explains that chimney cracks can let smoke into the home or expose the chimney's components to high temperatures that may cause a fire. It recommends professional inspection. A crack reaching the flue isn't cosmetic.
Why the other choices are weaker
- A. A crack into the flue path is a venting and fire concern, not an appearance issue.
- C. Exterior caulk is not evidence of a suitable repair for a damaged flue. The chimney needs qualified evaluation before use.
- D. A stove that lights doesn't prove the venting is safe.
Sources: EPA Burn Wise, Wood-Burning Installation and Maintenance (Annual Inspections: chimney cracks, smoke entry and heat/fire concerns); EBPHI content outline — topic coverage (Domain 1, Task 12, A.8–A.9 (typical defects; safety issues); coverage, not a technical-answer source)
Item ID: NHIE-D1T12-01
Question 16 of 60
Domain 2 · What was inspected and how · Describing the electrical service
Which report entry BEST describes the electrical service?
A. Overhead service drop; main panel in the garage; main breaker labeled 200 amps; copper service-entrance conductors.
B. Electrical system appears adequate for the size and age of the home.
C. Panel appears older than the rest of the house and should be upgraded to modern equipment with more capacity at some point.
D. Service is about 100 amps, based on the square footage of the house.
Show answer and explanation for Question 16
Correct answer: A. Overhead service drop; main panel in the garage; main breaker labeled 200 amps; copper service-entrance conductors.
EBPHI's outline asks you to describe systems by their distinguishing characteristics, such as type, size, and location. This entry tells the client what's there and where, using what you observed, such as the breaker's label.
Why the other choices are weaker
- B. "Adequate" describes nothing. It gives no type, size, or location.
- C. That's an opinion with no description, and it implies a defect you haven't identified.
- D. Service size comes from labeling and equipment, not a guess from square footage.
Sources: EBPHI exam overview packet and content outline (Domain 2, Task 1: describe inspected systems by type, size and location)
Item ID: NHIE-D2T1-01
Question 17 of 60
Domain 1 · Interior · Uneven stair risers
Using the 2021 IRC riser-uniformity criterion, an interior stair has risers that are 7 inches high, except the bottom riser, which is 8 inches. What should you report?
A. Acceptable, because an 8-inch riser is close enough to the 7-inch risers.
B. A trip hazard: riser heights vary by more than model code allows; recommend correction.
C. Acceptable, as long as a sturdy, graspable handrail runs the full length of the stair from the bottom step to the top.
D. Note it only if the client mentions young children or older adults at home.
Show answer and explanation for Question 17
Correct answer: B. A trip hazard: riser heights vary by more than model code allows; recommend correction.
The 2021 IRC-based stair handout limits the difference between the largest and smallest riser in a flight to ⅜ inch. An 8-inch bottom riser beside 7-inch risers is a 1-inch difference—well beyond that limit. EBPHI lists improper riser height as a typical stair defect. Report the uneven risers as a trip concern and recommend correction.
Why the other choices are weaker
- A. A 1-inch difference is well past the ⅜-inch uniformity limit.
- C. A handrail helps but doesn't fix uneven risers.
- D. A trip hazard affects everyone, so report it either way.
Sources: MyBuildingPermit, Basic Stairs, Tip Sheet 01 (PDF p. 1, R311.7.5.1: maximum 3/8-inch riser variation); EBPHI content outline — topic coverage (Domain 1, Task 11, B.3 (improper riser height or tread depth); coverage, not a technical-answer source)
Item ID: NHIE-D1T11-01
Question 18 of 60
Domain 1 · Exterior · Deck ledger attachment
A deck is attached to the house rim joist with nails only. You see no bolts or lag screws through the ledger. What should you report?
A. Acceptable, as long as the nails are hot-dip galvanized for outdoor use.
B. Report the ledger attachment as improper; refer to a qualified contractor.
C. Recommend adding more nails to strengthen the ledger connection.
D. No comment, because the deck sits outside the main house structure.
Show answer and explanation for Question 18
Correct answer: B. Report the ledger attachment as improper; refer to a qualified contractor.
ICC's deck-safety guidance explains that nails subject to withdrawal must not be the sole ledger attachment. Its prescriptive examples use bolts or lag screws; an approved engineered connection is another possible route, but none is described here. Ledger failures can drop a deck suddenly, which is why EBPHI lists improper ledger attachment as a typical defect.
Why the other choices are weaker
- A. Corrosion resistance doesn't change the fact that nails alone aren't an acceptable ledger connection.
- C. More nails still leaves a nails-only connection subject to withdrawal. The appropriate connection must be evaluated, not guessed.
- D. Decks and their ledger attachment are listed in the NHIE outline.
Sources: ICC, Is Your Deck Safely Connected to Your House? (Ledger attachment discussion); EBPHI content outline — topic coverage (Domain 1, Task 2, C.3 (improper deck ledger attachment); coverage, not a technical-answer source)
Item ID: NHIE-D1T2-02
Question 19 of 60
Domain 3 · Integrity and objectivity · Contingent fee offer
You're an ASHI member. The listing agent offers to send you referrals and pay your fee, but only if your report lets the sale close. What should you do?
A. Accept it, as long as you disclose the arrangement to the buyer in writing.
B. Accept it, but let the agent review the report wording before it's sent.
C. Decline, because payment tied to the sale closing is a conflict of interest.
D. Accept it, provided the arrangement is written into your inspection contract.
Show answer and explanation for Question 19
Correct answer: C. Decline, because payment tied to the sale closing is a conflict of interest.
ASHI's Code of Ethics bars inspectors from working under arrangements where their pay or future referrals depend on the reported findings or on the sale closing. Even if you'd report honestly, the arrangement gives you a reason not to.
Why the other choices are weaker
- A. Disclosure doesn't cure a fee that depends on the result.
- B. That makes the conflict worse by giving an interested party influence over the findings.
- D. A contract term doesn't override an ethics rule against contingent compensation.
Sources: ASHI Code of Ethics (§1.B: no compensation or referrals contingent on findings or sale closing); EBPHI content outline — topic coverage (Domain 3, Task 2, item 2 (conflicts of interest); coverage, not a technical-answer source)
Item ID: NHIE-D3T2-01
Question 20 of 60
Domain 1 · Electrical · Double-tapped breaker
In the main panel, two branch-circuit conductors are clamped under a single terminal screw on one breaker. The manufacturer identifies this terminal for one conductor only. What should you report?
A. Acceptable, because both of the connected circuits have power.
B. Recommend the client move one of the two wires to an open breaker space in the panel to separate the circuits.
C. Report it as an overfused circuit that needs a smaller breaker.
D. A double-tapped breaker; recommend correction by a licensed electrician.
Show answer and explanation for Question 20
Correct answer: D. A double-tapped breaker; recommend correction by a licensed electrician.
The manufacturer permits one conductor at this terminal, but two are installed. That is the defect. Some terminals are identified for more than one conductor, so the mere presence of two wires is not enough without checking the terminal's identification. Report this connection for electrician correction.
Why the other choices are weaker
- A. Working circuits don't make the connection safe.
- B. Panel work belongs to an electrician, not the client.
- C. Overfusing means a breaker or fuse too large for the wire. This is a different defect.
Sources: OSHA, Electrical General Requirements (1910.303(c)(2)(ii), terminals for more than one conductor must be identified); EBPHI content outline — topic coverage (Domain 1, Task 5, B.9 (double-tapping, overfusing, loose connections); coverage, not a technical-answer source)
Item ID: NHIE-D1T5-02
Question 21 of 60
Domain 1 · Site conditions · Grading toward the house
The soil beside one wall slopes toward the foundation. After rain, water ponds against that wall, and there's no surface drain to carry it away. Which conclusion is directly supported by what you saw?
A. The groundwater table has risen above the basement floor.
B. An underground footing drain has collapsed.
C. The foundation waterproofing membrane has ruptured.
D. Surface runoff is being directed toward the foundation.
Show answer and explanation for Question 21
Correct answer: D. Surface runoff is being directed toward the foundation.
The slope and the ponding show a surface-drainage problem. PNNL's guide calls preventing water from saturating the soil around the foundation the best defense against foundation water intrusion, which is why grade should carry runoff away. That observation shows a moisture risk. It doesn't prove any hidden component has failed.
Why the other choices are weaker
- A. You didn't observe the groundwater level. This assumes a hidden condition.
- B. Nothing in the observations shows the condition of a buried drain.
- C. The membrane is concealed. This is a diagnosis the facts don't support.
Sources: PNNL, Final Grade Slopes Away from Foundation (Scope and Description); EBPHI content outline — topic coverage (Domain 1, Task 1, A.3 (negative grade, poor drainage); coverage, not a technical-answer source)
Item ID: NHIE-D1T1-02
Question 22 of 60
Domain 2 · Defects and failures · Older water heater
A tank water heater's data plate shows it was made 17 years ago. It's working and you see no leaks or corrosion. Which report entry is BEST?
A. Report its age and condition; suggest budgeting for replacement without predicting failure.
B. Report it as defective and needing replacement, because a unit this old shouldn't be counted on even though it works.
C. State that it should last about three more years before failing.
D. Leave out its age, because the unit is working with no visible leaks.
Show answer and explanation for Question 22
Correct answer: A. Report its age and condition; suggest budgeting for replacement without predicting failure.
EBPHI's outline expects you to know the expected service life of components. ASHI's Standard of Practice does not require a remaining-life prediction. The useful answer gives the client the facts (age, current condition) and context, without a forecast you can't support.
Why the other choices are weaker
- B. Age alone isn't a defect. It's working with no observed problems.
- C. A specific remaining-life prediction isn't supported by a visual inspection.
- D. Age is useful planning information the client would want.
Sources: ASHI Standard of Practice (§2.2.B.1 and §13.2.A.2: condition/service life and no required remaining-life prediction); EBPHI content outline — topic coverage (Domain 2, Task 3, item 1 (expected service life); coverage, not a technical-answer source)
Item ID: NHIE-D2T3-01
Question 23 of 60
Domain 1 · Roof · Shingle-style lapping
Which arrangement of flashing or weather-resistive barrier layers sheds water correctly?
A. Each lower layer overlaps the layer above it.
B. Layers butt edge to edge with no overlap, sealed with caulk.
C. Any overlap direction works if the material is thick enough.
D. Each upper layer overlaps the layer below it, like shingles.
Show answer and explanation for Question 23
Correct answer: D. Each upper layer overlaps the layer below it, like shingles.
PNNL describes the principle as shingle-style lapping: the top layer of the weather-resistive barrier or flashing laps over the bottom layer so water can't drain behind the bottom layer. Gravity carries water down and out.
Why the other choices are weaker
- A. A reverse lap catches water and directs it behind the lower layer.
- B. Caulk alone ages and fails; the lap is what makes the detail drain.
- C. Thickness doesn't fix direction. Water follows the laps.
Sources: PNNL, Flashing at Roof-Wall Intersections in Existing Homes (Ensuring Success: shingle-style lapping); EBPHI content outline — topic coverage (Domain 1, Task 3, C.2 (flashing installation methods); coverage, not a technical-answer source)
Item ID: NHIE-D1T3-02
Question 24 of 60
Domain 1 · Plumbing and fuel distribution · Backsiphonage
A garden hose connected to an exterior hose bibb with no vacuum breaker is lying in a bucket of cleaning solution. A water main break suddenly drops the supply pressure. What could happen?
A. Nothing, because water can only flow outward through a hose bibb.
B. Backsiphonage could pull the solution into the potable water piping.
C. Thermal expansion in the piping could rupture the water heater tank.
D. The hose's washer screen would stop any reverse flow into the pipe.
Show answer and explanation for Question 24
Correct answer: B. Backsiphonage could pull the solution into the potable water piping.
EPA's cross-connection manual describes backsiphonage as atmospheric pressure forcing a pollutant liquid toward a potable supply that is under a vacuum. A submerged hose end plus a pressure drop is the classic setup. That's why EBPHI lists cross-connection as a typical water-supply defect.
Why the other choices are weaker
- A. Flow can reverse when supply pressure drops. That's exactly what backsiphonage is.
- C. Thermal expansion is a different issue and doesn't involve the hose.
- D. A screen filters debris; it isn't a backflow preventer.
Sources: EPA, Cross-Connection Control Manual (Chapter 3, printed pp. 12–15 / PDF pp. 18–21; submerged-hose examples in appendix); EBPHI content outline — topic coverage (Domain 1, Task 10, A.4 (cross-connection); coverage, not a technical-answer source)
Item ID: NHIE-D1T10-02
Question 25 of 60
Domain 1 · Structure · Notched floor joist
In the basement, a 2×10 sawn floor joist with an actual depth of 9¼ inches has a notch about 2 inches deep cut into its bottom edge at mid-span to clear a drain pipe. What should you report?
A. An improper notch in the middle third of the span; refer for evaluation and repair.
B. Acceptable, because a 2-inch notch is a small cut in a joist that is more than 9 inches deep.
C. Acceptable, because the notch is on the bottom edge rather than the top.
D. Recommend the client fill the notch with wood filler to restore strength.
Show answer and explanation for Question 25
Correct answer: A. An improper notch in the middle third of the span; refer for evaluation and repair.
Under the 2021 IRC rule summarized by ICC, notches in sawn joists are generally limited to one-sixth of the member's depth and are not allowed in the middle third of the span. End notches have a separate one-fourth-depth limit. Here, 9¼ ÷ 6 is about 1.54 inches, and the notch is about 2 inches deep at mid-span. It fails both the general depth limit and the location rule. EBPHI lists improper cuts and notches as typical floor-structure defects.
Why the other choices are weaker
- B. Depth isn't the only limit. The notch exceeds one-sixth of the stated depth (about 1.54 inches), and mid-span notches are not permitted.
- C. The middle-third prohibition applies to notches at either edge; being on the bottom does not make this cut acceptable.
- D. Wood filler is not a structural repair for a cut joist; the altered member needs qualified evaluation.
Sources: ICC CodeNotes, IRC Cutting, Drilling and Notching (PDF pp. 1–2, R502.8.1 and sawn-lumber table); EBPHI content outline — topic coverage (Domain 1, Task 4, B.4 (improper cuts and notches); coverage, not a technical-answer source)
Item ID: NHIE-D1T4-02
Question 26 of 60
Domain 1 · Life safety · Garage-to-house door
The door between an attached garage and the kitchen has neither a self-closing nor an automatic-closing device. It stays wherever you leave it and only latches if pushed firmly. What should you report?
A. A fire-separation safety concern: provide self-closing or automatic-closing operation and self-latching.
B. Acceptable, because the door is solid wood and fits its frame well.
C. Recommend the owners keep the door shut whenever a car is running.
D. No comment, since interior doors are outside the scope of the inspection.
Show answer and explanation for Question 26
Correct answer: A. A fire-separation safety concern: provide self-closing or automatic-closing operation and self-latching.
The door between a garage and the living space is part of the separation that slows fire and car exhaust from reaching the house. The 2021 International Residential Code requires it to be self-closing (or automatic-closing) and self-latching. Older homes may have been built under earlier rules, so describe it as a safety concern and recommend correction.
Why the other choices are weaker
- B. Door construction matters, but a door left open doesn't separate anything.
- C. Relying on habit doesn't fix the missing closer.
- D. This is a fire-separation door, which EBPHI's outline covers under life safety.
Sources: MyBuildingPermit, Residential Garage Separation, Tip Sheet 06 (PDF p. 2, Doors, R302.5.1); EBPHI content outline — topic coverage (Domain 1, Task 13, item 2 (fire separation, fire-rated doors); coverage, not a technical-answer source)
Item ID: NHIE-D1T13-02
Question 27 of 60
Domain 2 · Further evaluation and urgent action · CO alarm sounding
Midway through the inspection, a carbon monoxide alarm in the hallway goes into its full alarm pattern. It isn't the low-battery chirp. What should you do first?
A. Find the source by checking each fuel-burning appliance in turn.
B. Silence the alarm, keep inspecting, and note the event in the report.
C. Get everyone outside to fresh air and call emergency services.
D. Open the hallway window and continue the inspection with care.
Show answer and explanation for Question 27
Correct answer: C. Get everyone outside to fresh air and call emergency services.
CPSC's guidance is direct: when a CO alarm sounds, immediately move outside to fresh air and call emergency services or 911, and don't try to locate the source yourself. Carbon monoxide is colorless and odorless, so you can't judge it by feel. Reporting comes later.
Why the other choices are weaker
- A. CPSC advises against hunting for the source. Get out first.
- B. Silencing a real alarm and staying inside ignores an emergency.
- D. One open window doesn't make the house safe. Leave and call for help.
Sources: CPSC, Carbon Monoxide Fact Sheet (What should I do when my CO alarm sounds?); EBPHI content outline — topic coverage (Domain 2, Task 4, item 3 (CO accumulation); coverage, not a technical-answer source)
Item ID: NHIE-D2T4-02
Question 28 of 60
Domain 1 · Heating · Soot at a gas furnace
On a gas furnace, you see heavy soot around the burner compartment opening. What is the BEST report entry?
A. Cosmetic soot from normal gas-furnace operation; no action is needed.
B. Evidence of a combustion problem; recommend qualified HVAC evaluation before further operation.
C. A cracked heat exchanger is causing the soot, so recommend replacing the furnace before the heating season.
D. Recommend raising the thermostat setting to cut down on short cycling.
Show answer and explanation for Question 28
Correct answer: B. Evidence of a combustion problem; recommend qualified HVAC evaluation before further operation.
HUD's inspection guide identifies soot as evidence of poor combustion and calls for qualified attention to the burner and venting. The soot is observable; a specific failed heat-exchanger part is not. Report the condition and recommend qualified HVAC evaluation before further operation.
Why the other choices are weaker
- A. Heavy soot is not a basis for declaring normal, satisfactory combustion.
- C. That diagnosis goes beyond what you observed.
- D. Changing the thermostat setting does not evaluate or correct the combustion problem.
Sources: HUD, Residential Rehabilitation Inspection Guide, part 3 (PDF p. 25 / printed p. 86: soot, poor combustion and qualified furnace attention); EBPHI content outline — topic coverage (Domain 1, Task 7: heating-system combustion and safety; coverage only)
Item ID: NHIE-D1T7-02
Question 29 of 60
Domain 1 · Insulation, moisture and ventilation · Frost in the attic
On a cold winter morning, you find frost on the underside of the roof sheathing above the bathrooms. You also see gaps around recessed light housings and the top plates of interior walls. What's the most likely explanation?
A. The roof covering is leaking above the bathrooms, and the water froze on the sheathing overnight.
B. Moist house air is leaking into the attic and condensing on cold sheathing.
C. Attic frost is normal in winter and doesn't need to be reported.
D. The gaps need more insulation piled on top to stop the moisture.
Show answer and explanation for Question 29
Correct answer: B. Moist house air is leaking into the attic and condensing on cold sheathing.
PNNL explains that warm, moisture-laden house air leaking into a cold attic can cause condensation and frost on cold surfaces. The gaps you found are a plausible pathway, and the cold sheathing is where the moisture collects. Report both and recommend air-sealing evaluation; this pattern does not by itself rule out other moisture sources.
Why the other choices are weaker
- A. A roof leak is possible, but the cold sheathing and air gaps support condensation from indoor air as the best explanation given.
- C. Repeated condensation can wet and damage sheathing; it's a reportable moisture condition.
- D. Piling on batt or loose-fill insulation does not establish an air barrier and can create problems around heat-producing fixtures. The leakage paths need proper evaluation.
Sources: PNNL, Air Sealing Attic Access Panels/Doors/Stairs (Region: warm moist house air entering a cold attic can produce condensation/frost); EBPHI content outline — topic coverage (Domain 1, Task 8, B.3 (moisture movement, attic air bypasses); coverage, not a technical-answer source)
Item ID: NHIE-D1T8-02
Question 30 of 60
Domain 3 · Pre-inspection agreement · When to sign the agreement
The buyer's agent, who has no authority to sign for the client, suggests the client can sign your pre-inspection agreement when you deliver the report. What is the BEST response?
A. Accept, since the finished report will explain all the limitations.
B. Have the agent sign on the client's behalf to save everyone time.
C. Skip the agreement entirely if the client pays the fee in advance.
D. Have the client receive and sign it before the inspection begins.
Show answer and explanation for Question 30
Correct answer: D. Have the client receive and sign it before the inspection begins.
EBPHI's outline treats the timing of delivering and signing the agreement as a core professional responsibility. An agreement signed after the work can't set expectations for that work. Check your state's rules too.
Why the other choices are weaker
- A. The point of the agreement is to settle scope and limits before the work, not describe them afterward.
- B. An authorized representative can act for the client, but the question expressly says this agent has no signing authority.
- C. Payment isn't a substitute for an agreed scope and terms.
Sources: EBPHI exam overview packet and content outline (Domain 3, Task 1: client or authorized representative; agreement delivery/signing timing)
Item ID: NHIE-D3T1-02
Question 31 of 60
Domain 1 · Cooling · Weak airflow and a clogged filter
During cooling, airflow from the supply registers is weak. The return filter is visibly packed with dust. What is supported by these observations?
A. The clogged filter is restricting airflow; recommend replacement and service.
B. The compressor has failed, which explains the weak airflow, so the outdoor unit should be replaced.
C. The system is low on refrigerant and needs to be recharged.
D. The thermostat is defective and is calling for too little cooling.
Show answer and explanation for Question 31
Correct answer: A. The clogged filter is restricting airflow; recommend replacement and service.
The DOE notes that a clogged filter restricts airflow through the unit and reduces its ability to cool. That's what you can see. Concluding that the compressor or refrigerant charge has failed would go beyond your evidence.
Why the other choices are weaker
- B. Nothing observed shows compressor failure.
- C. Nothing in these observations establishes the refrigerant charge. That requires an appropriate service evaluation.
- D. A thermostat problem isn't indicated by weak airflow at the registers.
Sources: U.S. DOE, Energy Saver 101: Home Cooling (PDF p. 1: clogged/dirty filter reduces airflow and cooling); EBPHI content outline — topic coverage (Domain 1, Task 6, B.3 (dirty air filter); coverage, not a technical-answer source)
Item ID: NHIE-D1T6-02
Question 32 of 60
Domain 1 · Mechanical exhaust · Bath fan into the attic
In the attic, the bathroom exhaust fan's duct has come loose and is blowing into the insulation. What should you report?
A. Acceptable, because the humid air still leaves the bathroom.
B. Improper exhaust termination; recommend connecting it to the exterior.
C. Recommend removing the fan, since the attic is already ventilated.
D. Report it only if mold is already visible on the attic sheathing.
Show answer and explanation for Question 32
Correct answer: B. Improper exhaust termination; recommend connecting it to the exterior.
PNNL's bathroom-exhaust guidance calls for ducting to the outdoors, not into an attic or other enclosed building space. A fan that dumps humid air into the attic just moves the moisture problem upstairs. Report the disconnected duct and recommend correction.
Why the other choices are weaker
- A. The fan's job is to get moist air out of the house, not into the attic.
- C. Attic ventilation isn't designed to handle bathroom moisture dumped into it.
- D. Report the defect now; waiting for damage helps no one.
Sources: PNNL, Bathroom Exhaust Fans (Scope, duct termination to outdoors); EBPHI content outline — topic coverage (Domain 1, Task 9, A.5 (improper termination); coverage, not a technical-answer source)
Item ID: NHIE-D1T9-02
Question 33 of 60
Domain 2 · Limitations · Smart thermostat limits
The home has a smart thermostat that runs the HVAC system through an app. The sellers aren't present and the device is locked without their login. You can't change modes at the thermostat. What should you report?
A. That the heating and cooling system is satisfactory, since the thermostat display was on and showed the current temperature.
B. That the smart thermostat is defective and should be replaced by a technician.
C. Nothing, because smart-home devices fall outside the scope of every inspection.
D. That the HVAC couldn't be fully operated; recommend confirming it once access is available.
Show answer and explanation for Question 33
Correct answer: D. That the HVAC couldn't be fully operated; recommend confirming it once access is available.
EBPHI's outline specifically includes limitations caused by smart and emerging technology. When a device prevents normal operation, your report should say what you couldn't test and why, so the client can follow up.
Why the other choices are weaker
- A. You couldn't operate it. You can't report it as satisfactory.
- B. Being locked isn't the same as being broken.
- C. Smart-home limitations are named in the outline; the client needs to know what wasn't tested.
Sources: EBPHI exam overview packet and content outline (Domain 2, Task 2: limitations from smart and emerging technologies); ASHI Standard of Practice (§2.2.B.4: what was not inspected and why)
Item ID: NHIE-D2T2-02
Question 34 of 60
Domain 1 · Fireplaces and fuel-burning appliances · Gas logs and the damper
A masonry fireplace has a Real Fyre G4 vented gas log set installed. The damper can be closed completely, and there is no clamp or stop to keep it partly open. What should you report?
A. Acceptable, because closing the damper saves heat when the logs are off.
B. Recommend removing the damper so it can never be closed again.
C. A missing damper stop, a safety issue; refer to a qualified gas fireplace pro.
D. Report it only if soot stains are visible on the mantel or hearth.
Show answer and explanation for Question 34
Correct answer: C. A missing damper stop, a safety issue; refer to a qualified gas fireplace pro.
The G4 manual requires a fixed minimum permanent chimney opening and a fully open damper while the unit burns. The damper clamp prevents full closure. Here, neither a clamp nor another permanent stop is present, and the damper closes completely. Report the venting safety concern and recommend qualified correction before use.
Why the other choices are weaker
- A. With vented logs, the risk is someone lighting them with the damper closed.
- B. The manual permits alternatives when a clamp does not fit, but choosing or performing an alteration requires qualified installation judgment. Removal is not the only answer.
- D. The missing stop is the defect; you don't need to wait for evidence of spillage.
Sources: Robert H. Peterson, Real Fyre G4 Vented Gas Log Sets: Installation and Owner’s Manual (PDF p. 8, Damper Clamp Instructions and Minimum Permanent Free Opening); EBPHI content outline — topic coverage (Domain 1, Task 12, B.9 (missing/damaged damper stop, improper venting); coverage, not a technical-answer source)
Item ID: NHIE-D1T12-02
Question 35 of 60
Domain 1 · Electrical · GFCI versus AFCI
A client asks how a GFCI differs from an AFCI. Which answer is correct?
A. They do the same job; AFCI is simply the newer name manufacturers use for the familiar GFCI device.
B. A GFCI is designed to prevent fires, while an AFCI is designed to prevent shocks.
C. AFCI protection eliminates the need for overcurrent protection on that circuit.
D. GFCI: trips on current imbalance to cut shock risk. AFCI: detects arcing to cut fire risk.
Show answer and explanation for Question 35
Correct answer: D. GFCI: trips on current imbalance to cut shock risk. AFCI: detects arcing to cut fire risk.
OSHA explains that a GFCI interrupts power when the outgoing and returning current differ by about 5 milliamperes. CPSC explains that AFCIs address fire hazards from arcing, while GFCIs address shock hazards. Ordinary breakers may not respond to arcing until a fire has started.
Why the other choices are weaker
- A. They protect against different hazards: shock versus arcing fire.
- B. That's reversed.
- C. Arc-fault and overcurrent protection are different functions, even when one breaker provides both.
Sources: OSHA, Ground-Fault Circuit Interrupters (How GFCIs compare outgoing and returning current); CPSC Pub. 5133, Arc-Fault Circuit Interrupters (Single page: AFCI purpose; GFCI distinction); EBPHI content outline — topic coverage (Domain 1, Task 5, B.6 (GFCI, AFCI); coverage, not a technical-answer source)
Item ID: NHIE-D1T5-03
Question 36 of 60
Domain 1 · Exterior · Glass beside an entry door
Beside an entry door is a clear glass sidelite. It is in the same wall plane as the closed door, with no intervening wall or barrier. Its edge is within 24 inches of the door, and its bottom edge is 18 inches above the floor (the walking surface). You find no safety-glazing identification or other certification for it. What should you report?
A. Acceptable, because the sidelite is insulated double-pane glass that is in good condition with intact seals.
B. Tap the glass firmly to find out whether it's tempered before reporting.
C. Safety glazing is expected here and none was identified; refer to a glazing contractor.
D. No comment, because the glass is clean, intact, and in good condition.
Show answer and explanation for Question 36
Correct answer: C. Safety glazing is expected here and none was identified; refer to a glazing contractor.
The 2021 IRC-based glazing handout identifies this same-plane location within 24 inches of a door and below 60 inches as requiring safety glazing, subject to its listed exceptions. Safety glazing can have several kinds of permanent identification, and laminated glass has a certification alternative. With neither identification nor certification established here, report that safety glazing could not be verified and refer for confirmation or correction—not that an absent etched mark alone proves ordinary glass.
Why the other choices are weaker
- A. Double-pane doesn't mean safety glass.
- B. Testing by impact is unsafe and won't tell you the glass type.
- D. Condition isn't the issue; the glass type in this location is.
Sources: MyBuildingPermit, Safety Glazing, Tip Sheet 19 (PDF p. 1: R308.1 identification, R308.4.2 glazing adjacent to doors); EBPHI content outline — topic coverage (Domain 1, Task 2, B.4 (safety glazing); coverage, not a technical-answer source)
Item ID: NHIE-D1T2-03
Question 37 of 60
Domain 2 · Defects and failures · Dishwasher won't run
The installed dishwasher doesn't start when you use its normal controls. The breaker is on and other kitchen outlets work. Which report entry is supported?
A. The control board has failed, since the breaker is on and power reaches the kitchen; the dishwasher must be replaced.
B. It's satisfactory, because it looks clean and shows no damage.
C. Note only that a dishwasher is present in the kitchen.
D. It didn't operate using normal controls; refer to an appliance technician.
Show answer and explanation for Question 37
Correct answer: D. It didn't operate using normal controls; refer to an appliance technician.
ASHI's Standard of Practice includes activating an installed dishwasher's primary function with normal controls. You observed a failure to operate. Naming a specific failed internal part would be a diagnosis you didn't make.
Why the other choices are weaker
- A. You didn't open or test the appliance, so you can't name the failed part.
- B. Appearance doesn't show function, and it didn't run.
- C. A non-operating appliance is a reportable finding.
Sources: ASHI Standard of Practice (§10.1.F: installed dishwashing machine normal controls; §2.2.B reporting); EBPHI content outline — topic coverage (Domain 1, Task 11, D.2 (normal controls); Domain 2, Task 3; coverage, not a technical-answer source)
Item ID: NHIE-D2T3-02
Question 38 of 60
Domain 1 · Plumbing and fuel distribution · Galvanized supply piping
An older home has galvanized steel water supply pipes. When you run the kitchen faucet and an upstairs shower together, flow at the shower drops sharply. What should you report?
A. Reduced functional flow with galvanized piping; refer to a qualified plumber.
B. Normal, because every house loses some pressure with two fixtures running.
C. The water heater is undersized and can't keep up with two fixtures.
D. The municipal water supply pressure to the house is too low.
Show answer and explanation for Question 38
Correct answer: A. Reduced functional flow with galvanized piping; refer to a qualified plumber.
HUD's inspection guide explains that corrosion and mineral deposits can reduce flow through galvanized steel piping. Your job is to report the flow you observed and the piping type, and refer it, not to guess the inside condition.
Why the other choices are weaker
- B. A sharp drop is a functional-flow problem worth reporting.
- C. An undersized storage capacity would not explain this observed functional-flow drop; the evidence does not establish a water-heater defect.
- D. Possible, but you didn't measure it, and the galvanized pipe is an observed likely factor.
Sources: HUD, Residential Rehabilitation Inspection Guide, part 3 (PDF p. 11 / printed p. 72: galvanized supply corrosion/deposits and reduced flow); EBPHI content outline — topic coverage (Domain 1, Task 10, A.5 (galvanized piping; functional flow); coverage, not a technical-answer source)
Item ID: NHIE-D1T10-03
Question 39 of 60
Domain 1 · Life safety · Bedroom window bars
A ground-floor bedroom has one required emergency escape and rescue window and no alternative qualifying opening. That window has fixed security bars on the outside, with no release that can be opened from inside the room. What should you report?
A. An emergency escape hazard; recommend bars with an inside release.
B. Acceptable, because the bars improve the home's security.
C. Recommend the client keep a key for the bars next to the window.
D. No comment, because security bars count as personal property.
Show answer and explanation for Question 39
Correct answer: A. An emergency escape hazard; recommend bars with an inside release.
The code-based emergency-escape handout requires bars over the required opening to be releasable or removable from inside without a key, tool or special knowledge. Fixed bars with no inside release block that escape route.
Why the other choices are weaker
- B. Security doesn't outweigh blocked emergency escape.
- C. The release must not depend on finding or using a key; the stated bars also have no inside release.
- D. Installed bars affect life safety, which is in scope.
Sources: MyBuildingPermit, Residential Emergency Egress Openings, Tip Sheet 10 (PDF pp. 1–2, release/removal of bars and covers from inside); EBPHI content outline — topic coverage (Domain 1, Task 13, item 1 (egress, window security bar release); coverage, not a technical-answer source)
Item ID: NHIE-D1T13-03
Question 40 of 60
Domain 1 · Roof · Vent boot and attic stain
On the roof, the rubber boot around a plumbing vent pipe is cracked. In the attic, directly below, the sheathing has a dark water stain. What is the BEST report approach?
A. Report only the attic stain, since the cracked boot is a minor item.
B. Report only the boot, since the attic stain could be an old one.
C. Recommend the client seal the crack with roofing cement right away.
D. Report both and their likely connection; refer to a roofing contractor.
Show answer and explanation for Question 40
Correct answer: D. Report both and their likely connection; refer to a roofing contractor.
HUD's roof-inspection guidance calls for checking cracked or brittle flashing around roof penetrations and looking for associated interior water evidence. Linking the cracked boot to the stain below helps explain the concern, but it does not prove that the boot is the only source or that leakage is active now. Report both and refer for roofing evaluation.
Why the other choices are weaker
- A. The cracked boot is a plausible entry point and is itself a reportable defect.
- B. The stain is relevant evidence of past or present wetting, even if its timing is unknown.
- C. A guessed surface patch does not establish a suitable repair or evaluate the stained sheathing.
Sources: HUD, Residential Rehabilitation Inspection Guide, part 2 (§2.5–2.6 roof penetrations, flashing and interior water evidence); EBPHI content outline — topic coverage (Domain 1, Task 3, D.3 (deteriorated boot/collar); Domain 2, Task 4, item 2 (relationships); coverage, not a technical-answer source)
Item ID: NHIE-D1T3-03
Question 41 of 60
Domain 3 · Integrity and objectivity · Sharing the report
You're an ASHI member. The seller's agent asks you for a copy of the buyer's inspection report. Nothing in the report involves an urgent safety hazard, and no law requires you to share it. What should you do?
A. Get the client's permission before releasing the report.
B. Send it, because the report becomes public once the inspection is done.
C. Send it, because the agent is involved in the sale.
D. Send it, because the seller owns the house.
Show answer and explanation for Question 41
Correct answer: A. Get the client's permission before releasing the report.
ASHI's Code of Ethics requires inspectors to protect client confidentiality, with a limited exception related to safety hazards. EBPHI's outline also lists report confidentiality under protecting the client's interest. Client confidentiality, not an assumption about copyright ownership, controls the disclosure in this scenario.
Why the other choices are weaker
- B. Reports aren't public documents.
- C. Being part of the transaction doesn't give the other side's agent a right to your client's report.
- D. Owning the property doesn't make the seller your client.
Sources: ASHI Code of Ethics (§2.C: client confidentiality and safety-hazard exception); EBPHI content outline — topic coverage (Domain 3, Task 2, item 4 (report confidentiality); coverage, not a technical-answer source)
Item ID: NHIE-D3T2-02
Question 42 of 60
Domain 1 · Structure · Cut roof trusses
In the attic, several truss web members have been cut out to make room for storage. There's no sign of added framing or engineering paperwork. What should you report?
A. Acceptable, as long as the roof line shows no visible sagging yet.
B. Modified trusses; refer to a design professional such as a structural engineer.
C. Recommend nailing the cut web pieces back into their original spots.
D. Report it only as a limitation of the attic inspection, since the stored items blocked a full view of the framing.
Show answer and explanation for Question 42
Correct answer: B. Modified trusses; refer to a design professional such as a structural engineer.
Trusses are engineered systems: each web carries load as part of the whole. Removing webs can change how the roof carries load. The 2021 IRC-based framing checklist requires registered design-professional approval for truss alterations. Report the cut members and refer for that evaluation; a straight roof line is not approval of the alteration.
Why the other choices are weaker
- A. Damage can exist before sagging shows.
- C. Nailing pieces back in is not evidence of an approved engineered repair.
- D. It's a structural concern, not just an access issue.
Sources: Town of Topsham, Residential Framing Inspection Checklist (PDF p. 5, alterations to trusses, R802.10.4); EBPHI content outline — topic coverage (Domain 1, Task 4, D.4 (modified/damaged trusses); coverage, not a technical-answer source)
Item ID: NHIE-D1T4-03
Question 43 of 60
Domain 2 · What was inspected and how · Infrared camera findings
Your infrared camera shows a cool patch on a ceiling below a bathroom. What's the BEST next step before you report it?
A. Report an active roof leak based on the infrared image alone.
B. Check the area with a moisture meter and report what you confirm.
C. Report that the infrared image shows mold inside the ceiling.
D. Ignore it, because infrared scans aren't required in an inspection.
Show answer and explanation for Question 43
Correct answer: B. Check the area with a moisture meter and report what you confirm.
FLIR's technical guidance explains why a suspected moisture pattern needs confirmation. An infrared camera shows surface temperature differences, not water itself. A moisture meter helps confirm whether the cool spot is wet.
Why the other choices are weaker
- A. A temperature pattern alone does not confirm moisture or establish a roof leak.
- C. Infrared cameras don't detect mold.
- D. You saw something; follow up within your tools and report it.
Sources: FLIR, How to Detect a Water Leak with Thermal Imaging (Moisture patterns and verification with a moisture meter); EBPHI content outline — topic coverage (Domain 2, Task 1, item 4 (test instruments and their proper use); coverage, not a technical-answer source)
Item ID: NHIE-D2T1-02
Question 44 of 60
Domain 1 · Interior · Range anti-tip bracket
On a 30-inch GE electric range with a removable storage drawer, the manufacturer's visual inspection method shows that the required anti-tip bracket is missing. What should you report?
A. Acceptable, because ranges are heavy enough not to tip in normal use.
B. Recommend the client avoid opening the oven door all the way.
C. A missing or ineffective anti-tip bracket; recommend correction.
D. No comment, since a freestanding range is a personal-property appliance.
Show answer and explanation for Question 44
Correct answer: C. A missing or ineffective anti-tip bracket; recommend correction.
GE's guidance requires an anti-tip bracket and describes a visual check for this range configuration. A missing bracket leaves a tip-over hazard. Report the missing safety component and recommend installation according to the range's instructions; do not press on the open oven door to demonstrate tipping.
Why the other choices are weaker
- A. The manufacturer requires anti-tip protection; the range's weight is not a substitute.
- B. That's a workaround, not a fix.
- D. This is an installed cooking appliance included in the inspection, with a manufacturer-required safety component.
Sources: GE Appliances, Range Anti-Tip Bracket (Inspecting Anti-Tip Installation Using the Visual Method, 30-inch electric range with removable drawer); EBPHI content outline — topic coverage (Domain 1, Task 11, D.4 (missing anti-tip bracket); coverage, not a technical-answer source)
Item ID: NHIE-D1T11-02
Question 45 of 60
Domain 1 · Site conditions · Soil against wood
Along one side of the house, soil and mulch are piled up against the bottom of the wood siding. What should you report?
A. Acceptable, as long as the mulch is a naturally decay-resistant type such as cedar or redwood.
B. Earth-to-wood contact; recommend restoring clearance and checking for damage.
C. Recommend painting the bottom edge of the siding to seal it.
D. Report it only if termites or their mud tubes are visible.
Show answer and explanation for Question 45
Correct answer: B. Earth-to-wood contact; recommend restoring clearance and checking for damage.
HUD's wall-cladding guidance calls for checking wood near the ground for decay and maintaining separation from earth. Soil and mulch against wood can hold moisture and conceal damage. Report the contact, recommend restoring clearance, and have the affected siding checked rather than declaring a hidden insect infestation.
Why the other choices are weaker
- A. The type of mulch doesn't change wood-to-soil contact.
- C. Paint doesn't fix the contact or the moisture it holds.
- D. Report the condition that creates the risk; don't wait for damage.
Sources: HUD, Residential Rehabilitation Inspection Guide, part 2 (§2.1: wood cladding near the ground, decay and clearance); EBPHI content outline — topic coverage (Domain 1, Task 1, A.3 (earth-to-wood contact); coverage, not a technical-answer source)
Item ID: NHIE-D1T1-03
Question 46 of 60
Domain 2 · Further evaluation and urgent action · Known problem panel
The main panel is a Federal Pacific Stab-Lok. You see no burn marks or loose parts. What should your report say?
A. Report the panel as satisfactory, because there are no burn marks, loose parts, or other visible defects.
B. State that the panel will fail and must be replaced immediately.
C. Recommend the client swap in new Stab-Lok breakers as a precaution.
D. Name the brand, note it's a known problem panel type, and refer to an electrician.
Show answer and explanation for Question 46
Correct answer: D. Name the brand, note it's a known problem panel type, and refer to an electrician.
EBPHI's outline lists Federal Pacific Stab-Lok among known problem electrical panels. In its historical investigation, CPSC reported failed calibration tests on certain breakers but closed the investigation without determining the safety of FPE breakers. A clean appearance does not establish trip performance. Name the panel and recommend electrician evaluation without claiming a recall, inevitable failure or an official finding that all such panels are safe.
Why the other choices are weaker
- A. No visible burning is not evidence that the breakers will trip correctly under fault conditions.
- B. That's a prediction you can't support from a visual inspection.
- C. Panel work belongs to an electrician, not the client.
Sources: CPSC, Commission Closes Investigation of FPE Circuit Breakers (Investigation findings and explicit limits of safety determination); EBPHI content outline — topic coverage (Domain 1, Task 5, B.8 (known problem panels); Domain 2, Task 4, item 1; coverage, not a technical-answer source)
Item ID: NHIE-D2T4-03
Question 47 of 60
Domain 1 · Heating · Separated vent connector
The vent connector from a gas furnace to the chimney has pulled apart at a joint. There's soot around the gap. What is the BEST report entry?
A. A maintenance item to mention at the next scheduled furnace service.
B. Push the joint back together, then continue with the inspection.
C. Recommend installing a carbon monoxide alarm near the furnace, with no other action needed on the vent itself.
D. A combustion-gas safety hazard; inform the occupants and recommend HVAC correction before further operation.
Show answer and explanation for Question 47
Correct answer: D. A combustion-gas safety hazard; inform the occupants and recommend HVAC correction before further operation.
HUD's inspection guide calls for sound, properly fitted vent connections; CPSC identifies fuel-burning heating and venting defects as carbon-monoxide concerns. A separated connector provides a path for combustion products to escape. Inform the occupants and recommend qualified correction before further operation. If a CO alarm sounds or an exposure is suspected, leave and call emergency services.
Why the other choices are weaker
- A. A disconnected vent is a safety hazard, not routine maintenance.
- B. Pushing the joint together does not establish a secure, properly supported or safe vent repair.
- C. An alarm helps, but it doesn't fix the open vent.
Sources: HUD, Residential Rehabilitation Inspection Guide, part 3 (PDF p. 25 / printed p. 86: vent connections); CPSC, Carbon Monoxide Fact Sheet (Heating-system and venting precautions; emergency response); EBPHI content outline — topic coverage (Domain 1, Task 7, C.5 (separated vent, back drafting); coverage, not a technical-answer source)
Item ID: NHIE-D1T7-03
Question 48 of 60
Domain 1 · Insulation, moisture and ventilation · Sealed crawl space
A crawl space has a sealed plastic liner on the floor and walls, insulated walls, a conditioned-air supply, and no vents to the outside. The liner is intact and dry. The client asks whether you'll recommend adding vents. What's the BEST answer?
A. Yes, because every crawl space needs vents to the outdoors.
B. Yes, because a sealed plastic liner traps ground moisture under the house unless outdoor vents let it escape.
C. No; this conditioned crawl space is designed without vents, so inspect it as designed.
D. Only if the client plans to store belongings in the crawl space.
Show answer and explanation for Question 48
Correct answer: C. No; this conditioned crawl space is designed without vents, so inspect it as designed.
PNNL describes unvented insulated crawlspaces with ground-moisture control, sealed boundaries and a conditioning or drying strategy. Adding outdoor vents simply because none are present could work against that design. Look for liner damage, moisture, and conditioning problems instead; the observations do not certify every part of the assembly.
Why the other choices are weaker
- A. An intentionally unvented crawlspace does not need outdoor vents merely because it is a crawlspace.
- B. A sealed ground liner is intended to control ground moisture. Its presence is not, by itself, a reason to add outdoor vents.
- D. Storage plans don't change how the space is designed to work.
Sources: PNNL, Unvented Insulated Crawlspaces (Scope and Description: ground vapor control, sealed insulated assembly and conditioning/drying); EBPHI content outline — topic coverage (Domain 1, Task 8, C.5 (conditioned/encapsulated attics and crawl spaces); coverage, not a technical-answer source)
Item ID: NHIE-D1T8-03
Question 49 of 60
Domain 2 · Defects and failures · Writing the defect clearly
Under the hall bathroom sink, the drain trap is dripping, and the cabinet floor is stained and swollen. Which report entry is BEST?
A. "Hall bath sink: trap leaking, cabinet floor swollen; ongoing leaks can cause decay and mold. Recommend a plumber."
B. "Plumbing issue noted in the bathroom area; recommend further review."
C. "Hall bath sink trap failed due to its age; recommend replacing all of the bathroom's supply and drain plumbing."
D. "Minor drip at the hall bath sink, typical of older homes; monitor."
Show answer and explanation for Question 49
Correct answer: A. "Hall bath sink: trap leaking, cabinet floor swollen; ongoing leaks can cause decay and mold. Recommend a plumber."
A good defect entry says what, where, what you saw, why it matters, and who should handle it. EBPHI's outline lists common defects and the implications of not repairing them. EPA explains that moisture can support mold growth.
Why the other choices are weaker
- B. Too vague. It doesn't say where, what was seen, or who should fix it.
- C. It assumes a cause and recommends far more than the finding supports.
- D. It downplays visible water damage, and "monitor" isn't a real next step for an active leak.
Sources: EPA, A Brief Guide to Mold, Moisture and Your Home (Mold Basics: moisture can support mold growth); EBPHI exam overview packet and content outline (Domain 2, Task 3: description and implications of defects)
Item ID: NHIE-D2T3-03
Question 50 of 60
Domain 1 · Fireplaces and fuel-burning appliances · Wood fuel condition
A homeowner complains that their wood stove smokes and doesn't heat well. The firewood is freshly cut and stacked uncovered on bare ground. What's the BEST explanation?
A. The stove needs scrap lumber or pallets mixed in to burn hotter.
B. The wood isn't seasoned; wet wood makes more smoke and less heat.
C. Fresh-cut wood burns cleaner because it still holds natural oils.
D. Fuel moisture doesn't affect how a wood stove burns or heats.
Show answer and explanation for Question 50
Correct answer: B. The wood isn't seasoned; wet wood makes more smoke and less heat.
EPA's Burn Wise guidance (an archived program page) says wood burns best below 20 percent moisture content, recommends seasoning for at least six months, and notes that wet wood causes excess smoke and wastes energy. Seasoning time alone does not guarantee that the wood is dry enough; a moisture reading checks the result. EBPHI's outline includes fuel types and combustion characteristics.
Why the other choices are weaker
- A. Painted, treated, or glued wood can release harmful chemicals and damage the appliance.
- C. Moisture, not oil content, is the issue here, and wet wood burns worse.
- D. It's one of the biggest factors in smoke and heat output.
Sources: EPA Burn Wise, Best Wood-Burning Practices (Building a Fire; Safe Wood-Burning Practices; What Not to Burn); EBPHI content outline — topic coverage (Domain 1, Task 12, A.6 (fuel types, combustion characteristics); coverage, not a technical-answer source)
Item ID: NHIE-D1T12-03
Question 51 of 60
Domain 1 · Electrical · Hot receptacle
A standard kitchen receptacle (not a dimmer or other device that normally runs warm) is hot to the touch while a toaster is plugged in. What should you report?
A. An overheating receptacle; stop using it until an electrician checks it.
B. Normal, because a toaster draws a lot of power from the circuit.
C. Recommend using a different kitchen receptacle for the toaster.
D. Recommend a higher-amp breaker so the kitchen circuit can keep up.
Show answer and explanation for Question 51
Correct answer: A. An overheating receptacle; stop using it until an electrician checks it.
CPSC advises that unusually warm or hot outlets should not be used until an electrician checks them, because an unsafe connection can start a fire. EBPHI lists overheating among common panel and wiring safety issues.
Why the other choices are weaker
- B. A receptacle shouldn't get hot under normal use.
- C. That leaves the faulty receptacle in place.
- D. A larger breaker doesn't fix a hot connection and can make overheating worse.
Sources: CPSC Pub. 513, Home Electrical Safety Checklist (Outlets and Switches, printed p. 7 / PDF p. 4); EBPHI content outline — topic coverage (Domain 1, Task 5, B.10 (overheating); coverage, not a technical-answer source)
Item ID: NHIE-D1T5-04
Question 52 of 60
Domain 3 · Pre-inspection agreement · Work outside the agreed scope
Your signed agreement covers the main house and attached garage and expressly excludes a detached shed. On site, the client asks you to look at the shed too. What's the BEST response?
A. Inspect the shed quietly as a courtesy and add a short note about it at the end of the report.
B. Explain it's out of scope; amend the agreement in writing before inspecting it.
C. Tell the client it's fine, since it looks sound from the yard.
D. Refuse to discuss the shed at all and move on with the inspection.
Show answer and explanation for Question 52
Correct answer: B. Explain it's out of scope; amend the agreement in writing before inspecting it.
The pre-inspection agreement defines scope. EBPHI's outline frames the agreement around establishing the rights and responsibilities of both parties. Changing the scope on the fly without documenting it invites misunderstandings about what was inspected.
Why the other choices are weaker
- A. Undocumented scope changes blur what the client paid for and what you're responsible for.
- C. You can't vouch for something you didn't inspect.
- D. You can decline or amend the scope, but you should explain the situation.
Sources: EBPHI exam overview packet and content outline (Domain 3, Task 1: written agreement and scope of services)
Item ID: NHIE-D3T1-03
Question 53 of 60
Domain 1 · Mechanical exhaust · Heat recovery ventilator
The home has a heat recovery ventilator (HRV). It doesn't run when you use its wall control. What should you report?
A. Acceptable, because the house has operable windows for fresh air.
B. Recommend disconnecting the HRV to save energy year-round.
C. It didn't operate using normal controls; refer to an HVAC contractor.
D. Measure its airflow and report whether the system is balanced.
Show answer and explanation for Question 53
Correct answer: C. It didn't operate using normal controls; refer to an HVAC contractor.
The HRV did not respond to its normal control, so its intended operation and operating air balance were not demonstrated. ASHI's Standard of Practice does not require forcing an inoperative system to run. Report what you observed and refer it.
Why the other choices are weaker
- A. Windows don't replace a ventilation system that's supposed to work.
- B. Disconnecting an installed system is not an evaluation or repair of its failure to operate.
- D. A system that is not running cannot demonstrate its operating airflow balance.
Sources: ASHI Standard of Practice (§13.2.C.1–2: systems inoperable or unresponsive to normal controls); EBPHI content outline — topic coverage (Domain 1, Task 9, B.4 (indoor air management: inoperative); coverage, not a technical-answer source)
Item ID: NHIE-D1T9-03
Question 54 of 60
Domain 1 · Roof · Roof you can't safely walk
A steep slate roof is wet from morning rain. You judge it unsafe to walk. What should you do?
A. Inspect from safe vantage points and report the method and limitations.
B. Walk the roof carefully anyway, since walking it is required.
C. Skip the roof entirely and leave it out of the report.
D. Report the roof as satisfactory, since no ceiling stains were seen.
Show answer and explanation for Question 54
Correct answer: A. Inspect from safe vantage points and report the method and limitations.
ASHI's Standard of Practice requires describing the roof-inspection method and reporting relevant limitations, but does not require entering areas or performing procedures judged dangerous. HUD also cautions against walking brittle slate during an inspection. Safety comes first, and the report should be honest about how the roof was viewed.
Why the other choices are weaker
- B. The stated conditions are unsafe; there is no requirement to walk this roof despite that risk.
- C. You can still inspect from safe vantage points, and the client needs to know what you could and couldn't see.
- D. Interior conditions don't substitute for viewing the roof.
Sources: ASHI Standard of Practice (§5.1.B.2; §13.2.D/F: roof inspection method and unsafe access); HUD, Residential Rehabilitation Inspection Guide, part 2 (§2.5, printed p. 18 / PDF p. 9: brittle slate and safe observation); EBPHI content outline — topic coverage (Domain 2, Task 1, item 3 (common inspection methods); coverage, not a technical-answer source)
Item ID: NHIE-D1T3-04
Question 55 of 60
Domain 2 · Further evaluation and urgent action · Connecting related findings
In the first-floor hallway, the ceiling has a water stain. Directly above it, the upstairs toilet is visibly loose at its base. What's the BEST report approach?
A. Report the ceiling stain as cosmetic and recommend repainting.
B. Report a probable roof leak above the hallway, since water stains on ceilings usually come from the roof.
C. Report both and their possible connection; refer to a plumber and check for damage.
D. Cut an opening in the ceiling to confirm the source of the water.
Show answer and explanation for Question 55
Correct answer: C. Report both and their possible connection; refer to a plumber and check for damage.
HUD's bathroom-inspection guidance connects fixture-area leak checks with examining ceilings below. Here, the loose toilet and the stain below it may be related, but they do not prove the source or extent of leakage. Linking the observations helps the client understand why plumbing evaluation and a check for damage are needed.
Why the other choices are weaker
- A. A stain below a loose toilet isn't just cosmetic.
- B. The observations justify investigating the fixture above; they do not establish a roof leak or rule out other sources.
- D. Invasive investigation is outside a visual inspection.
Sources: HUD, Residential Rehabilitation Inspection Guide, part 2 (§3.3, printed p. 29 / PDF p. 20: bathroom leaks and ceiling below); EBPHI content outline — topic coverage (Domain 2, Task 4, item 2 (relationships between components); coverage, not a technical-answer source)
Item ID: NHIE-D2T4-04
Question 56 of 60
Domain 1 · Plumbing and fuel distribution · Sump pump check valve
A basement sump pump discharges through a vertical pipe with no check valve. After the pump shuts off, you hear water rush back into the pit, and the pump starts again shortly after. What should you report?
A. Normal operation for a sump pump in a basement pit.
B. The pump is undersized for the amount of groundwater entering the pit, so it has to run more often.
C. Recommend the client unplug the pump between storms to rest it.
D. A missing check valve causing drainback and short-cycling; refer to a plumber.
Show answer and explanation for Question 56
Correct answer: D. A missing check valve causing drainback and short-cycling; refer to a plumber.
Without a functioning check valve, water in the vertical discharge pipe can fall back into the pit when the pump stops, so the pump re-pumps the same water. Zoeller's troubleshooting guidance links a missing or faulty check valve with frequent starts and stops. The observed drainback supports this finding rather than a guess about pump size.
Why the other choices are weaker
- A. Water rushing back and quick restarts aren't normal.
- B. The drainback, not pump size, explains what you observed.
- C. That could flood the basement during the next storm.
Sources: Zoeller, Three-Year-Warranty Pump Installation Instructions (PDF p. 2, Helpful Hints and Service Checklist C: starts/stops too often); EBPHI content outline — topic coverage (Domain 1, Task 10, F.4 (missing check valve); coverage, not a technical-answer source)
Item ID: NHIE-D1T10-04
Question 57 of 60
Domain 3 · Integrity and objectivity · Offering to repair
You're an ASHI member who also does roofing work. After you report a roof leak, the client asks you to quote paid repair work on that inspected roof for next week. What should you do?
A. Decline that work: ASHI restricts compensated repairs to covered systems within one year after inspection.
B. Quote it with a discount, since you already know the problem.
C. Quote it, as long as you disclose that you also do roofing.
D. Wait until after the sale closes, then provide the quote.
Show answer and explanation for Question 57
Correct answer: A. Decline that work: ASHI restricts compensated repairs to covered systems within one year after inspection.
ASHI's Code of Ethics bars compensated repairs, replacements or upgrades to systems or components covered by its Standard of Practice for one year after inspection. The proposed paid roof repair next week falls within that restriction. It removes an incentive to create repair work for yourself.
Why the other choices are weaker
- B. A discount doesn't remove the conflict.
- C. Disclosure doesn't cure the conflict under ASHI's rule.
- D. ASHI's restriction runs for a year after the inspection, not just until closing.
Sources: ASHI Code of Ethics (§1.F: compensated covered repair, replacement or upgrade within one year); EBPHI content outline — topic coverage (Domain 3, Task 2, item 2 (conflicts of interest); coverage, not a technical-answer source)
Item ID: NHIE-D3T2-03
Question 58 of 60
Domain 1 · Life safety · Painted sprinkler heads
Your agreed inspection includes a visual review of the accessible residential fire sprinkler heads. During a recent renovation, several sprinkler heads were painted over along with the ceiling. What should you report?
A. Painted sprinkler heads; refer to a fire-protection contractor.
B. Acceptable, because the paint color matches the ceiling.
C. Recommend the client scrape the paint off each head.
D. No comment, since sprinklers are outside a home inspection.
Show answer and explanation for Question 58
Correct answer: A. Painted sprinkler heads; refer to a fire-protection contractor.
Dyne's laboratory work shows that paint can interfere with sprinkler activation or spray distribution. That does not mean every painted head has necessarily failed, but painted heads need a qualified fire-protection contractor's evaluation. Report the visible condition without scraping, dismantling or trying to operate the heads.
Why the other choices are weaker
- B. Appearance doesn't matter; whether the head can work does.
- C. Tampering with sprinkler heads can damage them. That's a job for a qualified contractor.
- D. The question expressly includes this visual review in the agreement. It does not require a full functional test of the sprinkler system.
Sources: Dyne Fire Protection Labs, How Paint Affects Sprinkler Performance (Painted sprinkler testing: activation and spray distribution); EBPHI content outline — topic coverage (Domain 1, Task 13, item 4 (painted or blocked sprinkler heads); coverage, not a technical-answer source)
Item ID: NHIE-D1T13-04
Question 59 of 60
Domain 2 · Defects and failures · Explaining implications
At the tub, the caulk and grout along the joint where the tub meets the wall are cracked and partly missing. The drywall just outside the tub is soft. Which report entry BEST explains why the client should care?
A. "Caulk at the tub is worn; this is a routine maintenance item."
B. "Gaps at the tub joint can let water into the wall, damaging materials and promoting mold. Correct the water entry and evaluate the softened wall."
C. "Mold is growing inside the wall cavity behind the tub surround, and the area needs professional remediation."
D. "Replace the tub and surround to correct the condition."
Show answer and explanation for Question 59
Correct answer: B. "Gaps at the tub joint can let water into the wall, damaging materials and promoting mold. Correct the water entry and evaluate the softened wall."
The best entry connects the visible gap and soft drywall to a moisture concern and a useful next step. EPA advises correcting the water problem and drying or evaluating affected materials. Soft drywall does not prove hidden mold, and simply sealing over damage would leave its extent unresolved.
Why the other choices are weaker
- A. It treats the gap as routine upkeep and ignores the soft drywall and what could happen next.
- C. You didn't see inside the wall; that's an unsupported diagnosis.
- D. A repair prescription far beyond the finding, with no explanation.
Sources: EPA, A Brief Guide to Mold, Moisture and Your Home (Mold Cleanup Guidelines: fix water problems; dry and evaluate affected material); EBPHI content outline — topic coverage (Domain 2, Task 3, item 5 (implications if defects aren't repaired); coverage, not a technical-answer source)
Item ID: NHIE-D2T3-04
Question 60 of 60
Domain 1 · Structure · Two kinds of foundation cracks
One poured-concrete basement wall has a hairline vertical crack with no offset. Another wall has a wider crack where one side sits about ¼ inch out of plane from the other. Which report approach is BEST?
A. Report both cracks as normal concrete shrinkage.
B. Report both cracks as serious structural failure.
C. Describe both; refer the offset crack to a structural engineer.
D. Report neither, since basement walls commonly crack.
Show answer and explanation for Question 60
Correct answer: C. Describe both; refer the offset crack to a structural engineer.
Not every crack means the same thing. HUD's inspection guide distinguishes cracking and displacement patterns when evaluating foundation distress. A tight hairline crack and a crack with offset are different findings, so describe both and refer the displaced area for structural evaluation rather than calling both harmless or both failures.
Why the other choices are weaker
- A. The offset is a reason for further evaluation; these facts do not support dismissing it as harmless shrinkage.
- B. That overstates the hairline crack and can alarm the client unnecessarily.
- D. Cracks are a listed defect category; describe what you see.
Sources: HUD, Residential Rehabilitation Inspection Guide, part 2 (§4.4 masonry foundation distress and §4.9 concrete: distinguish crack/displacement observations); EBPHI content outline — topic coverage (Domain 1, Task 4, A.4 (typical defects: cracks, settlement); coverage, not a technical-answer source)
Item ID: NHIE-D1T4-04
Check your answers
Count how many you got right in each domain before looking at the answers. Domain 1 is the big one: it's 42 of these 60 questions, just as it's 70% of the outline.
For a practice percentage, divide first-attempt correct answers by questions you answered before revealing the explanation, then multiply by 100. Keep questions revealed first separate as review, not scored attempts. For example, 20 correct out of 25 checked is 80%, even if you reviewed another 10 answers without attempting them; 25 questions would still be untouched. With no checked answers, you have no practice percentage yet. (Official domain allocation, content outline.)
| Domain | Questions in this set | Question numbers |
|---|---|---|
| 1. Property and Building Inspection/Site Review | 42 | 1–3, 5, 6, 8–10, 12–15, 17, 18, 20, 21, 23–26, 28, 29, 31, 32, 34–36, 38–40, 42, 44, 45, 47, 48, 50, 51, 53, 54, 56, 58, 60 |
| 2. Analysis of Findings and Reporting | 12 | 4, 11, 16, 22, 27, 33, 37, 43, 46, 49, 55, 59 |
| 3. Professional Responsibilities | 6 | 7, 19, 30, 41, 52, 57 |
Show the full answer key
| # | Answer | Domain | Topic |
|---|---|---|---|
| 1 | C | 1 · Electrical | Aluminum branch wiring |
| 2 | C | 1 · Site conditions | Pool access barrier |
| 3 | A | 1 · Exterior | Garage door auto-reverse |
| 4 | C | 2 · Further evaluation and urgent action | Gas odor at the meter |
| 5 | D | 1 · Cooling | How air conditioning moves heat |
| 6 | C | 1 · Roof | Kick-out flashing |
| 7 | C | 3 · Pre-inspection agreement | Purpose of the pre-inspection agreement |
| 8 | B | 1 · Structure | Horizontal foundation crack |
| 9 | D | 1 · Plumbing and fuel distribution | Capped relief valve |
| 10 | A | 1 · Insulation, moisture and ventilation | Exposed insulation facing |
| 11 | D | 2 · Limitations | Blocked attic access |
| 12 | C | 1 · Mechanical exhaust | Dryer exhaust duct |
| 13 | B | 1 · Life safety | Smoke alarm coverage |
| 14 | D | 1 · Heating | Heat pump in heating mode |
| 15 | B | 1 · Fireplaces and fuel-burning appliances | Cracked chimney |
| 16 | A | 2 · What was inspected and how | Describing the electrical service |
| 17 | B | 1 · Interior | Uneven stair risers |
| 18 | B | 1 · Exterior | Deck ledger attachment |
| 19 | C | 3 · Integrity and objectivity | Contingent fee offer |
| 20 | D | 1 · Electrical | Double-tapped breaker |
| 21 | D | 1 · Site conditions | Grading toward the house |
| 22 | A | 2 · Defects and failures | Older water heater |
| 23 | D | 1 · Roof | Shingle-style lapping |
| 24 | B | 1 · Plumbing and fuel distribution | Backsiphonage |
| 25 | A | 1 · Structure | Notched floor joist |
| 26 | A | 1 · Life safety | Garage-to-house door |
| 27 | C | 2 · Further evaluation and urgent action | CO alarm sounding |
| 28 | B | 1 · Heating | Soot at a gas furnace |
| 29 | B | 1 · Insulation, moisture and ventilation | Frost in the attic |
| 30 | D | 3 · Pre-inspection agreement | When to sign the agreement |
| 31 | A | 1 · Cooling | Weak airflow and a clogged filter |
| 32 | B | 1 · Mechanical exhaust | Bath fan into the attic |
| 33 | D | 2 · Limitations | Smart thermostat limits |
| 34 | C | 1 · Fireplaces and fuel-burning appliances | Gas logs and the damper |
| 35 | D | 1 · Electrical | GFCI versus AFCI |
| 36 | C | 1 · Exterior | Glass beside an entry door |
| 37 | D | 2 · Defects and failures | Dishwasher won't run |
| 38 | A | 1 · Plumbing and fuel distribution | Galvanized supply piping |
| 39 | A | 1 · Life safety | Bedroom window bars |
| 40 | D | 1 · Roof | Vent boot and attic stain |
| 41 | A | 3 · Integrity and objectivity | Sharing the report |
| 42 | B | 1 · Structure | Cut roof trusses |
| 43 | B | 2 · What was inspected and how | Infrared camera findings |
| 44 | C | 1 · Interior | Range anti-tip bracket |
| 45 | B | 1 · Site conditions | Soil against wood |
| 46 | D | 2 · Further evaluation and urgent action | Known problem panel |
| 47 | D | 1 · Heating | Separated vent connector |
| 48 | C | 1 · Insulation, moisture and ventilation | Sealed crawl space |
| 49 | A | 2 · Defects and failures | Writing the defect clearly |
| 50 | B | 1 · Fireplaces and fuel-burning appliances | Wood fuel condition |
| 51 | A | 1 · Electrical | Hot receptacle |
| 52 | B | 3 · Pre-inspection agreement | Work outside the agreed scope |
| 53 | C | 1 · Mechanical exhaust | Heat recovery ventilator |
| 54 | A | 1 · Roof | Roof you can't safely walk |
| 55 | C | 2 · Further evaluation and urgent action | Connecting related findings |
| 56 | D | 1 · Plumbing and fuel distribution | Sump pump check valve |
| 57 | A | 3 · Integrity and objectivity | Offering to repair |
| 58 | A | 1 · Life safety | Painted sprinkler heads |
| 59 | B | 2 · Defects and failures | Explaining implications |
| 60 | C | 1 · Structure | Two kinds of foundation cracks |
Turn a miss into a review task
A wrong answer is only useful if you know why it was wrong. For every question you missed or guessed on, write one line in a log like this. Then cover the options and explain the principle out loud before you look at the question again.
| Question | What I got wrong | The principle in my own words | Source to revisit |
|---|---|---|---|
| 21 | I picked a hidden failure the facts didn't show. | Report what you saw (water directed at the wall), not a guess about what's buried. | PNNL: Final Grade Slopes Away from Foundation |
Look for patterns. Several misses on report wording (Domain 2) give you a reason to practice the "describe, explain why it matters, refer" habit; they don't establish how well you know the underlying systems. Misses clustered in one system, such as electrical or heating, point you to that chapter of your study material.
What your practice score means
Your result describes your answers to these 60 questions only. It isn't an NHIE score and it doesn't predict whether you'll pass.
The real exam is scored on a scale from 200 to 800, and 500 passes (EBPHI exam overview packet). That doesn't mean 500 out of 800 points, and it doesn't translate to 62.5% on this set. EBPHI converts raw scores to the scale so different versions of the exam can be compared fairly. Its candidate bulletin adds that your total isn't an average of domain sub-scores, and that questions vary in difficulty and importance (PSI candidate bulletin, "How the Test Is Scored").
With only 2 to 4 questions per topic here, one miss can swing a topic's percentage a lot. Use your results to pick what to study next, not to judge how ready you are.
PSI's Oklahoma bulletin describes a diagnostic report for unsuccessful candidates, organized by content area. That can help guide review alongside the misses you logged here; use the report and instructions issued by your own administrator. (PSI bulletin, “How the Test Is Scored.”)
How this set matches the NHIE content outline
The checked EBPHI content outline weights three domains at 70%, 20%, and 10% (EBPHI exam overview packet). This set uses 42, 12, and 6 questions respectively. Task counts below are an editorial rounding of the official shares to whole questions—not an exact reproduction of exam difficulty or every knowledge statement. Task names are shortened for navigation.
| Domain / task (official share) | Questions here | Question numbers |
|---|---|---|
| Domain 1: Property and Building Inspection/Site Review (70%) | 42 | |
| Task 1: Site conditions (5%) | 3 | 2, 21, 45 |
| Task 2: Exterior (5%) | 3 | 3, 18, 36 |
| Task 3: Roof (6%) | 4 | 6, 23, 40, 54 |
| Task 4: Structure (6%) | 4 | 8, 25, 42, 60 |
| Task 5: Electrical (7%) | 4 | 1, 20, 35, 51 |
| Task 6: Cooling (4%) | 2 | 5, 31 |
| Task 7: Heating (5%) | 3 | 14, 28, 47 |
| Task 8: Insulation, moisture and ventilation (5%) | 3 | 10, 29, 48 |
| Task 9: Mechanical exhaust (5%) | 3 | 12, 32, 53 |
| Task 10: Plumbing and fuel distribution (6%) | 4 | 9, 24, 38, 56 |
| Task 11: Interior (4%) | 2 | 17, 44 |
| Task 12: Fireplaces and fuel-burning appliances (6%) | 3 | 15, 34, 50 |
| Task 13: Life safety (6%) | 4 | 13, 26, 39, 58 |
| Domain 2: Analysis of Findings and Reporting (20%) | 12 | |
| Task 1: What was inspected and how (4%) | 2 | 16, 43 |
| Task 2: Limitations (4%) | 2 | 11, 33 |
| Task 3: Defects and failures (6%) | 4 | 22, 37, 49, 59 |
| Task 4: Further evaluation and urgent action (6%) | 4 | 4, 27, 46, 55 |
| Domain 3: Professional Responsibilities (10%) | 6 | |
| Task 1: Pre-inspection agreement (5%) | 3 | 7, 30, 52 |
| Task 2: Integrity and objectivity (5%) | 3 | 19, 41, 57 |
Task names above are our short labels; the official wording is in EBPHI's outline. Sixty questions can't cover every knowledge point in the outline, and this isn't a full-length exam. The real NHIE has 200 questions.
Is your study material on the current outline?
Check the domain weights against the outline supplied for your exam. The checked owner outline is 70% / 20% / 10%, with 13 Domain 1 tasks, including life safety equipment, and electrical content that includes electric vehicle service equipment. Older materials use 63% / 25% / 12%. PSI's transition bulletin contains the older outline and a later replacement outline in the same file; its cover retains an October 2019 update date while also announcing a 2024 transition. Do not use that cover date as proof that every page has the same version. Material still assigning 25% to reporting does not match the checked 70/20/10 outline.
What the real NHIE looks like
| Feature | NHIE information |
|---|---|
| Questions | 200 multiple choice in total, including 25 unscored pretest questions mixed in at random |
| Time | 4 hours |
| Format | Four answer choices; pick the BEST answer (some choices may be partly correct) |
| Scoring | Scaled from 200 to 800; 500 passes |
| Fee | The EBPHI overview packet lists $225 in most states and Canada; PSI's Oklahoma edition lists $195. Confirm the amount in your actual registration instructions. |
| Retakes | The owner packet says a 30-day wait and a separate fee, with unlimited attempts unless a state regulates otherwise. |
| Calculators | The owner packet prohibits calculators; the Oklahoma PSI edition permits a silent, non-programmable calculator. Use your actual administrator's written instructions rather than assuming the Oklahoma rule applies nationally. |
| Reference materials | The cited test-room instructions prohibit reference materials. |
Sources: EBPHI exam overview packet (PDF pp. 3–5); PSI candidate bulletin, Oklahoma edition, updated December 10, 2024 (PDF pp. 1, 11–14). Last verified: October 5, 2026 (the cited document passages for format, scoring, fees, retakes and outline; not a live registration quote).
How to handle "BEST answer" questions
The NHIE-specific opening of PSI's bulletin warns that some answer choices may be partly correct. That's why so many NHIE-style questions feel like two answers could work. In this set, the best answer usually does three things: it reports what you actually saw, it explains why that matters, and it sends the problem to the right person.
The weaker choices tend to fail in predictable ways. They call a problem acceptable, they guess at a hidden cause you didn't observe, or they prescribe a repair that the stated evidence and qualifications do not support. Question 49 is a good example. Every choice mentions the leaking trap, but only one says where it is, what it's damaging, and who should repair it, without blaming a cause you couldn't see.
Booking, fees, and retakes
Check the licensing authority and exam administrator named in your state's current instructions before paying. A state-specific PSI bulletin is not a national rule for eligibility, calculator use, cancellation or registration deadlines. The EBPHI overview packet explains that state administrators may have their own procedures.
Passing the NHIE isn't a license. Confirm the remaining application requirements with your state regulator and use the score-submission process that regulator specifies. Keep your appointment confirmation and the administrator's written rules for identification, permitted items and rescheduling.
Is there an official free NHIE practice test?
The official PSI bulletin includes five free sample questions and an answer key on PDF page 11. They are a short official sample, not a full-length exam. They are separate from Castleport's 60 original questions above.
The owner's reference list names the 2021 International Residential Code, the 2021 NFPA 101 Life Safety Code Handbook and the 2023 National Electrical Code. Use the current outline and reference instructions for your administration to check the editions in your study materials.
Sources and how we checked them
By the Castleport Test Prep Editorial Team. Last verified October 5, 2026.
We checked the cited exam-document passages and the technical sources linked beside the questions. The content outline supplies the topic map; agency guidance, standards and manufacturer instructions support the teaching principles. The domain allocation is exact at 42/12/6; task-level counts are rounded editorial choices. Code-based items identify the applicable study criterion, not the rules adopted in every local jurisdiction.
AI tools assisted with auditing and editing this page. Source checking is not qualified professional review, and no such review is claimed for this version. These are recognition, reporting and referral exercises—not instructions to repair equipment, alter structural members or perform hazardous tests. See our editorial standards.
Exam facts and free official sample
- EBPHI exam overview packet and content outline (©2023) — format, domain/task allocation, scoring, general fees/retakes and references.
- PSI candidate bulletin, updated December 10, 2024 (Oklahoma edition) — national-format opening; five free sample questions on PDF page 11; state-specific instructions clearly separated.
- PSI transition bulletin — historical comparison of old and replacement outlines, not current registration authority.
Sources used in the explanations
- CPSC Pub. 516, Repairing Aluminum Wiring — Permanent repairs and alternatives; PDF pp. 6–9, especially AlumiConn p. 8 and twist-on connectors p. 9.
- CPSC Pub. 362, Safety Barrier Guidelines for Residential Pools — Pedestrian gates, printed p. 11 / PDF p. 13.
- 16 CFR Part 1211, Safety Standard for Automatic Residential Garage Door Operators — §§1211.6–1211.8, particularly §1211.7 laboratory obstruction tests.
- New Jersey Natural Gas, Smell Gas? — Emergency instructions: leave, avoid ignition sources, telephone from a safe location.
- U.S. DOE, Energy Saver 101: Home Cooling — PDF p. 1, How an Air Conditioner Works and Common Air Conditioner Problems.
- PNNL, Flashing at Roof-Wall Intersections in Existing Homes — Scope; Description; Ensuring Success.
- HUD, Residential Rehabilitation Inspection Guide, part 2 — §2.1 wall cladding; §2.5–2.6 roofs; §3.3 bathrooms; §4.4 masonry foundations; §4.9 concrete.
- Watts TAG-100, T&P relief-valve safety instructions — Single-page safety tag: relief discharge must not be restricted; installation and service warnings.
- ASHI Standard of Practice — §2.2 reporting; §2.3 qualified additional services; §§5, 10–13 scope, normal controls, exclusions; revision notice above standard.
- Knauf, Faced vs. Unfaced Insulation — Facing/fire-safety discussion.
- CPSC Pub. 5022, Overheated Clothes Dryers Can Cause Fires — Single-page duct material, lint and airflow guidance.
- U.S. Fire Administration, Smoke Alarms — Opening placement recommendation; Where do I put smoke alarms?.
- ENERGY STAR, How Does a Heat Pump Work? — Heating/winter operation.
- EPA Burn Wise, Wood-Burning Installation and Maintenance — Annual Inspections: chimney cracks and professional inspection.
- MyBuildingPermit, Basic Stairs, Tip Sheet 01 — PDF p. 1, stair tread/riser text and Figure 1, R311.7.5.1.
- ICC, Is Your Deck Safely Connected to Your House? — Ledger attachment discussion.
- ASHI Code of Ethics — §1.B contingent compensation; §1.F compensated repair restriction; §2.C confidentiality.
- OSHA, Electrical General Requirements — 1910.303(c)(2)(ii), terminals for more than one conductor must be identified.
- PNNL, Final Grade Slopes Away from Foundation — Scope and Description.
- EPA, Cross-Connection Control Manual — Chapter 3, printed pp. 12–15 / PDF pp. 18–21; submerged-hose examples in appendix.
- ICC CodeNotes, IRC Cutting, Drilling and Notching — PDF pp. 1–2, R502.8.1 and sawn-lumber table.
- MyBuildingPermit, Residential Garage Separation, Tip Sheet 06 — PDF p. 2, Doors, R302.5.1.
- CPSC, Carbon Monoxide Fact Sheet — What should I do when my CO alarm sounds?; heating/venting precautions.
- HUD, Residential Rehabilitation Inspection Guide, part 3 — PDF p. 11 / printed p. 72: galvanized piping; PDF p. 25 / printed p. 86: furnace combustion and vents.
- PNNL, Air Sealing Attic Access Panels/Doors/Stairs — Region: warm moist house air entering a cold attic can produce condensation/frost.
- EPA, A Brief Guide to Mold, Moisture and Your Home — Mold Basics; Mold Cleanup Guidelines; Moisture Control; Hidden Mold.
- PNNL, Bathroom Exhaust Fans — Scope, duct termination to outdoors.
- Robert H. Peterson, Real Fyre G4 Vented Gas Log Sets: Installation and Owner’s Manual — PDF p. 8, Damper Clamp Instructions and Minimum Permanent Free Opening.
- OSHA, Ground-Fault Circuit Interrupters — How GFCIs compare outgoing and returning current.
- CPSC Pub. 5133, Arc-Fault Circuit Interrupters — Single page: AFCI purpose; GFCI distinction.
- MyBuildingPermit, Safety Glazing, Tip Sheet 19 — PDF p. 1: R308.1 identification, R308.4.2 glazing adjacent to doors.
- MyBuildingPermit, Residential Emergency Egress Openings, Tip Sheet 10 — PDF pp. 1–2, release/removal of bars and covers from inside.
- Town of Topsham, Residential Framing Inspection Checklist — PDF p. 5, alterations to trusses, R802.10.4.
- FLIR, How to Detect a Water Leak with Thermal Imaging — Moisture patterns and verification with a moisture meter.
- GE Appliances, Range Anti-Tip Bracket — Inspecting Anti-Tip Installation Using the Visual Method, 30-inch electric range with removable drawer.
- CPSC, Commission Closes Investigation of FPE Circuit Breakers — Investigation findings and explicit limits of safety determination.
- PNNL, Unvented Insulated Crawlspaces — Scope and Description: ground vapor control, sealed insulated assembly and conditioning/drying.
- EPA Burn Wise, Best Wood-Burning Practices — Building a Fire; Safe Wood-Burning Practices; What Not to Burn.
- CPSC Pub. 513, Home Electrical Safety Checklist — Outlets and Switches, printed p. 7 / PDF p. 4.
- Zoeller, Three-Year-Warranty Pump Installation Instructions — PDF p. 2, Helpful Hints and Service Checklist C: starts/stops too often.
- Dyne Fire Protection Labs, How Paint Affects Sprinkler Performance — Painted sprinkler testing: activation and spray distribution.
Two EPA pages above come from the Burn Wise program, which EPA stopped updating on October 30, 2025. We use them only for stable wood-burning and chimney basics. HUD's February 2000 guide is likewise used only for identified inspection principles, not as a current code or repair specification.
Castleport Test Prep is an independent exam prep publisher. We are not affiliated with, endorsed by, or approved by the Examination Board of Professional Home Inspectors (EBPHI) or PSI. NHIE and National Home Inspector Examination are names used to identify the exam; trademarks belong to their respective owners. These are original, unofficial practice questions, not actual or recalled exam questions. Practice results don't predict an NHIE score or guarantee licensure. Confirm licensing requirements with your state regulator.